Chapter 8 Network variable bindings
128
BAS-APG001-EN
UUKL binding list (actuator Open/Close or 
 
On/Off status)
Table 34 shows an example list of actuator status custom bindings. 
Actuator Open/Close or On/Off status is sent from the mechanical system 
directly to the FSCP. 
Table 34.  Actuator status custom bindings 
Function
Originator
Network variable
Destination
supplyFanStatus
Mechanical system
nvoSwitch01
MP580-3/nviSwitch04
returnFanStatus
Mechanical system
nvoSwitch02
MP580-4/nviSwitch03
 stairFanStatus
Mechanical system
nvoPercent01
MP580-2/nviPercent02
oaDamperStatus
Mechanical system
nvoPercent04
MP580-3/nviPercent01
raDamperStatus
Mechanical system
nvoPercent05
MP580-2/nviPercent01
eaDamperStatus
Mechanical system
nvoPercent06
MP580-4/nviPercent01
supplyDamperFloor01
Mechanical system
nvoPercent07
MP580-3/nviPercent02
returnDamperFloor01
Mechanical system
nvoPercent08
MP580-3/nviPercent03
supplyDamperFloor02
Mechanical system
nvoPercent09
MP580-3/nviPercent04
returnDamperFloor02
Mechanical system
nvoPercent10
MP580-3/nviPercent05
supplyDamperFloor03
Mechanical system
nvoPercent11
MP580-4/nviPercent02
returnDamperFloor03
Mechanical system
nvoPercent12
MP580-4/nviPercent03
supplyDamperFloor04
Mechanical system
nvoPercent13
MP580-4/nviPercent04
returnDamperFloor04
Mechanical system
nvoPercent14
MP580-4/nviPercent05