HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation
Optional components 46
Water distribution kit power requirements
Callout Specification
1
30 AT, 30 AF, 3P
2
Within facility 480V, 3 phase power distribution equipment
3
(3)#10, (1)#10G, 1"C. Feeder sized on a maximum run of
100 ft
4
Motor controller at skid
5
30 AT, 30 AF, 3P
6
20 AT, 3P
7
15 AT, 3P
8
(3)#12, (1)#12G ¾"C
9 P–1
10 P–2
11 UH–1
10 P–2
11 UH–1