HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation

Page de 63
 
Frequently asked questions  47 
Frequently asked questions 
HP POD frequently asked questions 
 
Question Answer 
Can I keep the HP POD on the trailer? 
Yes, if you choose to lease the trailer from HP or if your 
purchase your own trailer and have the HP POD installed on 
your trailer prior to shipment. You must also: 
 
Ensure that the site is stable and has been prepared 
correctly for the additional weight of the trailer. 
 
Provide a work platform to access exterior panels. 
What cooling capacity ranges are available 
in the HP POD? 
The HP POD is capable of cooling rack-mounted components 
consuming up to 605 kW of electrical power. 
What electrical power capacity ranges are 
available in the HP POD? 
The low density HP POD is capable of powering components up 
to 450 kW of electrical power. 
The high density HP POD is capable of powering components 
up to 605 kW of electrical power. 
Can the level of heat removal be regulated 
in proportion to the waste heat generated? 
Yes, the control system automatically adjusts the air flow to 
remove heat generated in the HP POD. 
How is water connected to the HP POD? 
There are two options to connect water: 
 
You directly connect your facility water to the HP POD, 
making sure the water meets the water requirements 
temperature, and flow rate. 
 
You connect your facility water to the water distribution kit, 
which is then connected to the HP POD through two 4-in 
150-psi hoses.
 
Does the HP POD require maintenance? 
Yes, general maintenance is outlined in this document. Contact 
HP service for additional information. 
Does condensation form? 
During normal operation some condensation might form, but the 
condensation does not reach any rack-mounted components or 
cause any damage. Excess condensation from the heat 
exchangers is collected and drained via three condensate 
drains ("
) across the rear of the HP 
POD. In most cases, the condensation evaporates prior to 
reaching the condensate drains. 
How does the HP POD control humidity? 
The relative humidity is maintained between 30–70%.  
If additional humidity is required, connect your facility water to 
the humidifier supply on the front of the HP POD. 
Does the air flow within the HP POD 
produce static electricity? 
The humidity of the HP POD is maintained between 30–70% to 
ensure that dangerous levels of static electricity cannot build.