HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation
Frequently asked questions 47
Frequently asked questions
HP POD frequently asked questions
Question Answer
Can I keep the HP POD on the trailer?
Yes, if you choose to lease the trailer from HP or if your
purchase your own trailer and have the HP POD installed on
your trailer prior to shipment. You must also:
your trailer prior to shipment. You must also:
•
Ensure that the site is stable and has been prepared
correctly for the additional weight of the trailer.
correctly for the additional weight of the trailer.
•
Provide a work platform to access exterior panels.
What cooling capacity ranges are available
in the HP POD?
The HP POD is capable of cooling rack-mounted components
consuming up to 605 kW of electrical power.
What electrical power capacity ranges are
available in the HP POD?
The low density HP POD is capable of powering components up
to 450 kW of electrical power.
The high density HP POD is capable of powering components
The high density HP POD is capable of powering components
up to 605 kW of electrical power.
Can the level of heat removal be regulated
in proportion to the waste heat generated?
Yes, the control system automatically adjusts the air flow to
remove heat generated in the HP POD.
How is water connected to the HP POD?
There are two options to connect water:
•
You directly connect your facility water to the HP POD,
making sure the water meets the water requirements
making sure the water meets the water requirements
) for quality,
temperature, and flow rate.
•
You connect your facility water to the water distribution kit,
which is then connected to the HP POD through two 4-in
150-psi hoses.
150-psi hoses.
Does the HP POD require maintenance?
Yes, general maintenance is outlined in this document. Contact
HP service for additional information.
HP service for additional information.
Does condensation form?
During normal operation some condensation might form, but the
condensation does not reach any rack-mounted components or
cause any damage. Excess condensation from the heat
cause any damage. Excess condensation from the heat
exchangers is collected and drained via three condensate
drains ("
) across the rear of the HP
POD. In most cases, the condensation evaporates prior to
reaching the condensate drains.
How does the HP POD control humidity?
The relative humidity is maintained between 30–70%.
If additional humidity is required, connect your facility water to
the humidifier supply on the front of the HP POD.
If additional humidity is required, connect your facility water to
the humidifier supply on the front of the HP POD.
Does the air flow within the HP POD
produce static electricity?
produce static electricity?
The humidity of the HP POD is maintained between 30–70% to
ensure that dangerous levels of static electricity cannot build.
ensure that dangerous levels of static electricity cannot build.