HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation

Page de 63
 
Frequently asked questions  48 
Question Answer 
Is the HP POD weather resistant? 
If there is an external leak, the HP POD is weatherproof and 
has sufficient protection against the encroachment of water 
inside the HP POD. 
What happens if there is an internal leak? 
If there is an internal leak, the water collects in the condensation 
drain pans or the water main drain pan. The additional water 
present in the condensation drain pan triggers a Leak Detection 
alarm, sent over the BMS. 
What will happen if water stops flowing to 
the HP POD? 
The building BMS receives a High Temperature alarm. An EPO 
will occur automatically if the hot aisle temperature exceeds 
66°C (150ºF). 
HP recommends shutting down all IT components or pressing 
any EPO button to manually power down the servers, to 
maintain server health, until the root problem can be solved. 
At what smoke level will an alarm be 
issued? 
You can set the four different ranges at which the ASSD panel 
smoke detector issues an alarm. For more information, see the 
smoke detector manual supplied with the HP POD. 
Can I switch out my servers and other rack-
mounted components? 
The HP POD supports any IT equipment that uses front to rear 
air flow cooling to maintain thermal integrity. 
If you must remove a server or other rack-mounted component 
for any prolonged period, you must replace it with a similar 
component or a heavy-duty blanking panel so that the HP POD 
interior can maintain thermal integrity. 
How will I be notified if there is an 
emergency in the HP POD? 
The smoke alarm automatically detects incipient fires and 
activates several different types of fire alarms:  
 
Visible—Internal and external HP POD strobes 
 
Audible—Horn 
 
Remote notification through the building fire alarm control 
panel (optional) 
Water emergencies are detected through the fire alarm control 
panel and drain trays, an alarm is initiated, and the building 
BMS is notified. 
If the fans are not functioning correctly, an alarm is initiated 
and the building BMS is notified.