HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation
Specifications 50
Specifications
HP POD specifications
Features Specifications
Dimensions
40 ft x 8 ft x 9.5 ft
Maximum weight
30,000 lb (empty)- 101,000 lb (fully-loaded)
Maximum power/ cooling
•
450 kW (Standard POD)
•
605 kW (High density POD)
Maximum rack quantity
22 racks
Rack Units (RU) per rack
50 RU
Rack Units (RU) maximum
1100 RU
Nominal power/ cooling per rack
25 kW
Maximum power/ cooling per rack
35 kW
Power input voltage
415 VAC, 3 Phase, 50/60 Hz, with neutral
Power distributed internally
Through 2 400A electrical busways
240/415 VAC, 50/60 Hz
240/415 VAC, 50/60 Hz
Customer access
Double-door on one end
Two 3 ft x 7 ft doors to the cold aisle (customer access)
Four 6 ft x 7 ft doors to the hot aisle (rear component access)
Two 3 ft x 7 ft doors to the cold aisle (customer access)
Four 6 ft x 7 ft doors to the hot aisle (rear component access)
Network supported
Bulk cable pass-through-fiber
Bulk cable pass-through-copper
(Optional) External rated DEMARC box
Bulk cable pass-through-copper
(Optional) External rated DEMARC box
Electrical specifications
Panel information
Feature
Electrical busway panel
House panel
Number of panels
•
2 (Standard HP POD)
•
3 (High density HP POD)
1
Amps (per panel)
400A
225A
Poles (per panel)
1
30–42
Phases 3
3
Circuit breaker information (Input)