HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation

Page de 63
 
Specifications 51 
    
Feature Specification 
Number of input circuit breakers 
2: 1 per panel 
Protection percentage 
80% 
Amps (per breaker) 
400A 
 
Fire alarm panel connections 
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the 
HP POD. 
 
Water specifications 
Water supply specifications without a water distribution kit 
 
Feature Specification 
Facility input temperature to HP POD 
12º to 24ºC (55º to 75ºF) 
Operating pressure 
137,895 to 172,369 Pa (20 to 
25 psi) 
Rated pressure max 
1,034,213 Pa (150 psi) 
HP POD pressure drop 
110,316 Pa (16 psi) 
HP POD water flow rate 
908.5 l/min (240 gal/min) 
Cooling water supply and return 
connections 
(2) 10.16 cm (4 inch) 150# 
flange 
Humidifier 
3.79 l/hr (1 gal/hr) domestic 
water from an alternate supply 
source 
 
Water supply specifications with a water distribution kit 
 
Feature Specification 
Facility input temperature to the water 
distribution kit 
4º to 10ºC (40º to 50ºF) 
Water distribution kit temperature output to 
the HP POD 
12º to 24ºC (55º to 75ºF) 
Operating pressure 
137,895 to 172,369 Pa (20 
to 25 psi) 
Rated pressure max 
1,034,213 Pa (150 psi) 
HP POD pressure drop 
110,316 Pa (16 psi) 
Water distribution kit pressure drop 
34,474 Pa (5 psi) max 
Water flow rate to the water distribution kit 
757 to 1,893 l/min (200 to 
500 gal/min) based on a 
facility operating delta T 
range of 6°to 12°C (10º–
20ºF) 
Water distribution kit flow rate to the HP POD 908.5 l/min (240 gal/min) 
Cooling water supply and return connections  (2) 10.16 cm (4 inch) 150# 
flange