Specifications 51
Feature Specification
Number of input circuit breakers
2: 1 per panel
Protection percentage
80%
Amps (per breaker)
400A
Fire alarm panel connections
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the
HP POD.
Water specifications
Water supply specifications without a water distribution kit
Feature Specification
Facility input temperature to HP POD
12º to 24ºC (55º to 75ºF)
Operating pressure
137,895 to 172,369 Pa (20 to
25 psi)
25 psi)
Rated pressure max
1,034,213 Pa (150 psi)
HP POD pressure drop
110,316 Pa (16 psi)
HP POD water flow rate
908.5 l/min (240 gal/min)
Cooling water supply and return
connections
(2) 10.16 cm (4 inch) 150#
flange
Humidifier
3.79 l/hr (1 gal/hr) domestic
water from an alternate supply
water from an alternate supply
source
Water supply specifications with a water distribution kit
Feature Specification
Facility input temperature to the water
distribution kit
4º to 10ºC (40º to 50ºF)
Water distribution kit temperature output to
the HP POD
12º to 24ºC (55º to 75ºF)
Operating pressure
137,895 to 172,369 Pa (20
to 25 psi)
to 25 psi)
Rated pressure max
1,034,213 Pa (150 psi)
HP POD pressure drop
110,316 Pa (16 psi)
Water distribution kit pressure drop
34,474 Pa (5 psi) max
Water flow rate to the water distribution kit
757 to 1,893 l/min (200 to
500 gal/min) based on a
facility operating delta T
facility operating delta T
range of 6°to 12°C (10º–
20ºF)
Water distribution kit flow rate to the HP POD 908.5 l/min (240 gal/min)
Cooling water supply and return connections (2) 10.16 cm (4 inch) 150#
Cooling water supply and return connections (2) 10.16 cm (4 inch) 150#
flange