Site Preparation
Liebert
®
 MC
10
Figure 6
Condenser planning dimensions—MCL055, MCL110, MCL165 and MCL220
Table 3
Condenser leg height and additional weight, MCL055, MCL110, MCL165 and MCK220
Model #
# of 
Fans
A
in. (mm)
B
in. (mm)
C
in. (mm)
D
in. (mm)
E
in. (mm)
Leg Height
F * In. (mm)
G
In. (mm)
H
In. (mm)
MCL055
1
68
(1727)
56
(1423)
54-3/8
(1381)
18 (457)
35-7/8
(911)
43-5/8
(1108)
MCL110
2
124-1/8
(3152)
112-1/8
(2848)
110-1/2
(2806)
36 (914)
53-7/8
(1368)
61-5/8
(1565)
MCL165
3
180-1/4
(4578)
73-7/16
(1866)
168-1/4
(4274)
110-1/2
(2806)
56-1/8
(1425)
48 (1219)
65-7/8
(1673)
73-5/8
(1870)
MCL220
4
236-5/16
(6003)
129-9/16
(3291)
224-3/8
(5699)
110-1/2
(2806)
112-1/4
(2851)
60 (1524)
77-7/8
(1978)
85-5/8
(2175)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths.
Source: DPN002416, Rev. 2
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting condenser
provided on 3&4 fan models
55-5/8"
(1413mm)
55-1/2"
(1409mm)
53-7/8"
(1368mm)
Electric Box End
48-3/4"
(1239mm)
Height to Top
of Fan Guard
DPN002416
Rev. 2
ANCHOR PLAN
Provided on
3- & 4- Fan Models
D
E
For typical footprint 
dimensions, see Figure 2