7.1  Menu Structure Continued…
Description
Select PV:
This menu allows the user to select the 
measurement that controls the transmitter’s
current output (mA).
This menu only appears if the interface        
(2 floats) option is provided.
Select Alarm:
The following alarm settings can be chosen:
“FailHigh” = 21.00mA
“FailLow”  = 3.50mA
“HoldOut” = holds last good reading until 
transmitter recovers.
Change Range:
This menu allows the user to change the measuring
range or span.  Enter the menu by changing the 
“No” to a “Yes” and press enter.
-   Select Lower Range Value (LRV):
This is the 4.00mA (0.00%) point on the senor.  This 
value should only be incremented.  For example if 
the value is changed from “0.00in” to “3.00in” the 
4.00mA point will shift 3.00 inches higher than the 
original point.  It is recommended to leave this at 
0.00 most of the time unless a special circumstance 
arises.  Press enter to go the next screen.
-   Select Upper Range Value (URV):
This is the 20.00mA (100.00%) point on the sensor.  
This value should only be decremented.  Changing 
this parameter will change the measuring range or 
span of the transmitter.
Select Damping:
This parameter is used to slow down the reaction of 
the instrument in order to ignore or average out 
any agitation on the process surface that may be 
causing an unsteady output.  The units are fixed in 
seconds and values can be from 1 to 26 seconds. 