Improper installation, adjustment, alteration, service or 
maintenance can cause injury or property damage. Refer 
to the owner’s information manual provided with this appli-
ance. For assistance or additional information consult a 
qualified installer, service agency or your dealer.
WARNING
The chart will help you in determining proper 
venting size according to the equivalent feet of 
pipe calculated above and the altitude above sea 
level of this installation.  Figure 11.2.
Locate the calculated equivalent feet of pipe on 
the vertical left side of the chart.  Move to the 
right horizontally on the chart until you reach 
your altitude above sea level.
If you fall below the diagonal line, 3 or 4 inch (76 
to 102mm) pipe may be used.  If it is anywhere 
above the diagonal line, a 4 inch (102mm) diam-
eter pipe is required.
The chart reveals that a 90° elbow is 5 times as 
restrictive to the flow of exhaust gases under 
positive pressure as 1 foot of horizontal pipe, and 
a foot of horizontal pipe is twice as restrictive as 
a foot of vertical pipe.
D.  Pipe Selection Chart
The table below can help you calculate the equivalent feet 
of pipe which is a method used to determine pellet vent size.  
Figure 11.1.
C.  Equivalent Feet of Pipe
2 ft.
2 ft.
3 ft.
2 ft.
Example of 3 Elbow-Rear Vent Termination Calculaton
Figure 11.1
Pellet Venting 
Component
# of 
Elbows
Feet of 
Pipe
Multipled 
By
Equivalent 
Feet
Components
Equivalent Feet
90
o
 Elbow or Tee
3
X
5
15
45
o
 Elbow
X
3
Horizontal Pipe
7
X
1
7
Vertical Pipe
2
X
0.5
1
Total Equivalent Feet
23
Note:  This is a generic example and is not 
intended to represent any specific fuel type.
Fire Risk.
Do NOT pack insulation or other 
combustibles between firestops.
•  ALWAYS maintain specified clearances 
around venting and firestop systems.
•  Install firestops as specified.
Failure to keep insulation or other material 
away from vent pipe may cause fire.
WARNING
3 in. or 4 in. (76mm or 102mm) Diameter  Pipe 
Equivalent Pipe 
Length In Feet
ALTITUDE IN THOUSANDS OF FEET 
20 
30 
   1        2       3       4       5       6        7       8        9     10
4 in. (102mm) Diameter Pipe Only 
10 
Example 1
Example 2
Figure 11.2
Example 1:  If the equivalent length of pipe is 23 
feet with altitude of 8,000 feet you must use 4 inch 
(102mm) diameter type “L” or “PL” vent.
Example 2:  If the equivalent length of pipe is 12 feet 
with altitude of 6,000 feet you may use 3 or 4 inch (76 
to 102mm) diameter type “L” or “PL” vent