ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
18 
 
alarm type/attributes  alarm status 
enter alarm 
delay time 
alarm 
suppression 
point in 
alarm 
no. of prepro-
grammed texts 
supplementary 
text 
user program reports 
always non-critical 
*DPD = datapoint description 
 
NOTE: 
A point is still seen as “in alarm” even when alarm suppression is 
enabled. 
 
 
Cycle Count 
The attribute "Cycle Count" contains the value indicating the number of transitions 
to the active state (see "Active State (prior to V2.04.x)" on page 14). 
 
 
Delay Time Switching Up 
This attribute is used in conjunction with flexible points of the type "feedback". It 
defines the delay time between switching upwards from one stage to another. The 
delay time affects every stage. The delay time also takes effect when switching, e.g. 
from manual value 0 to 2. In this case, it is switched from stage 0 to stage 1, then to 
stage 2 with the delay time between the switching processes. 
 
Range: 
 
0 to 255s 
Default value: 
10s 
Resolution:  
1s 
 
 
 
Fig. 8. Delay time switching up 
 
 
Delay Time Switching Down 
This attribute is used in conjunction with flexible points of the type "feedback". It 
defines the delay time between switching downwards from one stage to another. 
The delay time affects every stage. 
 
Range: 
 
0 to 255s 
Default value: 
10s 
Resolution: 
1s 
 
The feedback delay time starts to count after termination of delay time switching 
up/delay time switching down.