Honeywell R0512 Manuel D’Utilisation

Page de 86
EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
19 
 
 
Fig. 9. Delay time switching down 
 
 
Descriptors 
 
Informative descriptors 
A controller contains up to 128 physical datapoints and up to 256 pseudo 
datapoints. The Excel 100C provides 36 physical datapoints. An individual user 
address can be assigned to each of these 384 datapoints. 255 plain-language 
descriptors can be created with a maximum of 32 characters each. These 
descriptors are then assigned to datapoints in the datapoint description via the 
attribute "Descriptor". Descriptors complete the information concealed behind the 
user address. They can contain, for instance, a reference to a section of a building. 
The following list is an example of the relationship between user addresses and 
descriptors: 
 
User Address 
Descriptor 
Room temp floor 1 
Heating circuit, West wing 
Room temp floor 3 
Heating circuit, West wing 
Room temp floor 10 
Heating circuit, East 
Room temp corridor 
Heating circuit, East 
Flow temp floor 1 
Heating circuit, West wing 
Lights floor 1 
Building section V 
Lights corridor 
Building section V 
 
 
 
Engineering Unit 
The attribute "Engineering Unit" contains a list for selecting different engineering 
units for both analog datapoints (physical and pseudo), totalizer inputs (physical 
and pseudo), and digital datapoints. 
If, for instance, the external temperature is measured by an analog datapoint, the 
engineering unit of this datapoint must be set to "
°C" or "°F". If the electrical load is 
detected by a totalizer input, the engineering unit must be set to "kWh" for kilowatt-
hours. 
 
 
Feedback Delay 
The attribute "Feedback Delay" determines the time delay between, e.g. when a 
pump switched on (and detected) and when this status is made available to a 
program. 
 
 
High/Low Alarm/Warning Limits 
 
Specifying limit values 
In the case of analog inputs (e.g. inputs for sensing room temperature) and pseudo 
analog points (for instance, internally computed datapoints for the heating flow 
setpoint), two minimum and two maximum monitored limit values may be entered.