Troubleshooting
65
Table 23
Compressor and refrigeration system troubleshooting
Symptom
Possible Cause
Check or Remedy
Compressor will not 
start
Power off
Check main switch, fuses or CBs and wiring
Current overload open
Reset manually
Loose electrical connections
Tighten connections
Compressor motor burned out
Check and replace compressor if defective.
Compressor will not 
operate, contactor not 
pulling in
No call for cooling
Check monitor status.
Solenoid valve not energizing
Hold screwdriver over solenoid and check for magnetic field. 
This indicates solenoid is energized.
Low pressure switch not making 
contact
Check gas pressure - manually energize low pressure 
switch.
Compressor will not 
operate, contact not 
pulling in
High pressure switch open
Reset switch. Refer to other refrigeration troubleshooting 
suggestions.
Compressor contactor 
pulled in but 
compressor will not 
operate
Blown fuse or tripped CB
Check for line voltage after fuses or CBs, and after 
contactors.
Compressor runs for 
three minutes then 
stops; contactor drops 
out. Motor operates but 
valve won't open
Low pressure switch not closing
Check for low gas pressure. Compressor is running on 
Positive Start Kit (air cooled systems only).
Solenoid not opening
Check magnetic field to see if energized.
High discharge 
pressure
Dirty condenser or drycooler fins
Clean coil
Condenser equipment not 
operating
Check operation.
High refrigerant charge
Check refrigerant charge.
Hot gas bypass valve adjusted 
improperly
Adjust properly.
Water regulating valve adjusted 
improperly
Adjust properly.
Low discharge pressure
Excessive water now through 
condenser
Adjust water regulating valve
Suction service valve partially 
closed
Open the valve.
Leaky compressor suction valves
Pump down, remove the cylinder head, examine valves and 
valve seats; replace if necessary
Worn piston rings
Replace compressor.
Faulty head pressure control 
valve or condenser fan speed 
control
Replace if defective.
Low suction pressure
Insufficient refrigerant in system
Check for leaks, repair, and add refrigerant
Dirty air filters
Change filters.
Plugged filter-drier
Replace filter.
Improper superheat adjustment
Reset expansion valve for 10-15°F
Defective expansion valve 
sensing element
Replace element
Poor air distribution
Check duct work for closed dampers. Check for underfloor 
restrictions at or near the unit.
Low condensing pressure
Check head pressure control device.
Slipping belts
Inspect and adjust