Emerson DH Manuel D’Utilisation

Page de 80
Troubleshooting
67
Compressor continually 
cycles
Faulty low pressure switch
Repair or replace.
Dirt or restriction in tubing to 
pressure stat
Check and clean tubing.
Defective liquid line solenoid 
valve
Check valve and solenoid operator; replace if necessary.
Plugged filter-dryer
Replace filter
Compressor motor 
protectors tripping or 
cycling
High discharge pressure
Check for loss of condenser water or blocked condenser fan 
or coil.
Defective overload relay
Replace.
High suction temperature
Reduce suction temperature by expansion valve adjustment 
or provide desuperheating.
Loose power or control circuit 
wiring connection
Check all power and control circuit connections.
Defective motor
Check for motor ground or short. Replace compressor, if 
either condition is found.
Compressor cycles on 
locked rotor
Low line voltage
Check line voltage and determine location of voltage drop.
Seized compressor (remove 
bearing head assembly and 
attempt to rotate crankshaft)
Replace compressor.
Compressor motor defective
Check for motor winding short or ground.
Single phasing
Check voltage across all 3 legs at contactor. Correct source 
problem.
Liquid refrigerant condensing in 
cylinder
Check and replace valve plates.
Motor burnout
Check control panel for welded 
contactor contacts or welded 
overload contacts
Replace defective components.
Table 24
Dehumidification troubleshooting
Symptom
Possible Cause
Check or Remedy
No dehumidification
Control not calling for 
dehumidification
Check monitor status.
Compressor contactor not pulling in
See Compressor Section.
Compressor won't run; fuse blown 
or CB tripped
See Compressor Section. Check fuses or CBs and 
contacts. Check line voltage
Table 25
Glycol pumps troubleshooting
Symptom
Possible Cause
Check or Remedy
Suddenly stops 
pumping
Clogged strainer or impeller
Clean out debris.
Suddenly slow pumping
Clogged impeller, diffuser, or line
Clean out debris and use strainer.
Excessive leakage 
around the pump shaft 
while operating
Worn seal or packing
Replace seal or packing.
Performance poor
Worn impeller or seal
Replace with new impeller or seal.
Suction lift too high
Relocate pump closer to supply.
Motor not up to speed; low voltage
Larger lead wires may be required Check for proper 
line voltage (±10%).
Worn bearings
Replace pump
Noisy operation
Worn motor bearings
Replace pump
Low discharge head
Throttle discharge-improve suction conditions.
Debris lodged in impeller
Remove cover and clean out.
Cavitating pumps
Adjust system pressures.
Table 23
Compressor and refrigeration system troubleshooting (continued)
Symptom
Possible Cause
Check or Remedy