Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
7
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
3.0
M
ODBUS
 485 
AND
 M
ODBUS
 IP P
ROTOCOLS
3.1
Thermal Management Products
Table 6
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Status and Coil
Controller
Liebert iCOM
®
 v4
Liebert Products
Units with 
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status
Coil
Number
of Bits
Notes / Units
Extra Notes
Ext Reheat Lockout
10009
 - 
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Humidifier Lockout
10010
 - 
1
Active on Alarm
1, 2, 3, 4, 5, 6
Minimum Chilled Water Temp Set Point Enable
10013
13
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Return Air Sensor Event Control
10019
19
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Air Sensor A Event Control
10020
20
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Compressor Lockout
10021
 - 
1
Active on Alarm
1, 2, 3, 4, 5, 6
System On/Off Control
 - 
25
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Fan State
10025
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Cooling State
10026
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Free Cooling State
10027
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Hot Water / Hot Gas State
10028
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Electric Reheat State
10029
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Humidifier State
10030
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Dehumidifier State
10031
 —
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Main Fan Overload
10034
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Loss of Air Flow
10035
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Loss of Flow
10036
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure
10037
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure
10038
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload
10039
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue
10040
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure 2
10041
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure 2
10042
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload 2
10043
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6