Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
9
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Electric Reheater Hours Exceeded 2
10085
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Electric Reheater Hours Exceeded 3
10086
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Hot Water / Hot Gas Valve Hours Exceeded
10087
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Hours Exceeded
10088
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Dehumidifier Hours Exceeded
10089
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Unit Communication Lost
10091
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Master Unit Communication Lost
10092
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Unit Code Missing
10094
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Service Required
10098
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Control Board Not Detected
10099
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Customer Input 1
10104
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Customer Input 2
10105
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Customer Input 3
10106
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Customer Input 4
10107
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Temp Sensor Issue 1
10108
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Temp Sensor Issue 2
10109
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Supply Air Over Temperature
10209
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Supply Air Under Temperature
10210
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ambient Air Sensor Issue
10211
 —
1
Active on Alarm
2, 3, 4, 5, 6
Compressor Short Cycle 1
10212
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Short Cycle 2
10213
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Free Cooling Lockout
10214
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Reheater Over Temperature
10215
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Cylinder Worn
10216
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Under Current
10217
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Fan Issue
10218
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Condenser TVSS Issue
10219
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Condenser VFD Issue
10220
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Condenser Issue 1
10221
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Condenser Issue 2
10222
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
BMS Communications Timeout
10223
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Digital Output Board Not Detected 1
10224
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Digital Output Board Not Detected 2
10225
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Digital Output Board Not Detected 3
10226
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Table 6
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Status and Coil (continued)
Controller
Liebert iCOM
®
 v4
Liebert Products
Units with 
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status
Coil
Number
of Bits
Notes / Units
Extra Notes