Emerson MODBUS 485 Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
8
Compressor Pump Down Issue 2
10044
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Over Temp 1
10045
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Over Temp 2
10046
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Smoke Detected
10047
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Water Under Floor
10048
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Issue
10049
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Standby Glycol Pump On
10050
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Standby Unit On
10051
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Condenser Pump High Water
10052
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Return Air Sensor Issue
10053
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Loss of Air Blower
10055
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Low Water
10058
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Humidifier Over Current
10059
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Over Temperature
10060
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Shutdown - Loss Of Power
10061
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Supply Chilled Water Over Temp
10065
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Return Air Over Temperature
10067
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Return Air Under Temperature
10068
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
High Return Humidity
10069
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Low Return Humidity
10070
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Over Temperature
10071
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Under Temperature
10072
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity
10073
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Low Humidity
10074
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Supply Chilled Water Loss of Flow
10075
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Clogged Air Filter
10076
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Supply Air Sensor Issue
10077
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Free Cooling Temp Sensor Issue
10078
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Issue
10079
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Fan Hours Exceeded
10080
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Hours Exceeded 1
10081
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Hours Exceeded 2
10082
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Free Cooling Valve Hours Exceeded
10083
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Electric Reheater Hours Exceeded 1
10084
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Table 6
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller
Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status
Coil
Number
of Bits
Notes / Units
Extra Notes