Roberts Gorden BH15 Manuel D’Utilisation
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
8
SECTION 4: SPECIFICATIONS
4.1
Material Specifications
4.1.1
Combustion and Tubes
First 3 meters ALUMI-THERM
®
steel tubing.
Remaining tube 100 mm dia. 16 gauge heat treated
aluminised mild steel.
aluminised mild steel.
4.1.2
Reflectors
NS3 H14 aluminium or 1.4016 2R stainless
steel (option)
steel (option)
4.2
Heater Specifications
4.2.1
Sequence Controller
Fully automatic single try direct spark 100% shut off
ignition flame rectification module
ignition flame rectification module
4.2.2
Electrical
Rating: 230V, 50 Hz, single phase, 1 amp
Connection: 3 pin moulded plug
Connection: 3 pin moulded plug
4.2.3
Gas Supply
Connection: Rc1/2 (1/2" BSP int)
Natural :
Nominal - Inlet 1.13kPa
Maximum - Inlet 5.0 kPa
ULPG Gas (Propane or Propane/Butane mix):
Nominal - Inlet 2.75 kPa
Maximum - Inlet
Maximum - Inlet
5.00 kPa
4.3
Venting Specifications
4.3.1
Fans
BH-15, 20, 25, 30 ............ Model: Torin DSF 133-42
BH-35, 40, 45 .................. Model: Torin DSA 524-202
BH-50
BH-35, 40, 45 .................. Model: Torin DSA 524-202
BH-50
.................. Model: Magnetek JF1G
Consult the manufacturer for availability of alternate fans.
4.3.2
Flue
When fitted, the flue must be 100 mm, or greater in
diameter, and must conform to
diameter, and must conform to
AS5601/AG 601. The flue
must be self supporting. Inlet must be 100 mm diameter.
4.4
Suspension Specifications
Galvanised straight link welded chain.
Working load of 340 kg (750 lbs)
Working load of 340 kg (750 lbs)
4.5
Controls Specifications
Time switches, thermostats, etc. can be wired into the
electrical supply. External controls supplied as an
optional extra.
electrical supply. External controls supplied as an
optional extra.