Roberts Gorden BH15 Manuel D’Utilisation

Page de 25
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
SECTION 4: SPECIFICATIONS
4.1 
Material Specifications
4.1.1 
Combustion and Tubes
First 3 meters ALUMI-THERM
®
 steel tubing.
Remaining tube 100 mm dia. 16 gauge heat treated
aluminised mild steel.
4.1.2 
Reflectors
NS3 H14 aluminium or 1.4016 2R stainless
steel (option)
4.2 
Heater Specifications
4.2.1 
Sequence Controller
Fully automatic single try direct spark 100% shut off
ignition flame rectification module
4.2.2 
Electrical
Rating: 230V, 50 Hz, single phase, 1 amp
Connection: 3 pin moulded plug
4.2.3 
Gas Supply
Connection: Rc1/2 (1/2" BSP int)
Natural :
    Nominal - Inlet 1.13kPa
  Maximum - Inlet 5.0 kPa
ULPG Gas (Propane or Propane/Butane mix):
Nominal - Inlet 2.75 kPa
Maximum - Inlet 
5.00 kPa
4.3 
Venting Specifications
4.3.1 
Fans
BH-15, 20, 25, 30 ............ Model: Torin DSF 133-42
BH-35, 40, 45 .................. Model: Torin DSA 524-202
BH-50
.................. Model: Magnetek JF1G
Consult the manufacturer for availability of alternate fans.
4.3.2 
Flue
When fitted, the flue must be 100 mm, or greater in 
diameter, and must conform to 
AS5601/AG 601. The flue 
must be self supporting. Inlet must be 100 mm diameter.
4.4 
Suspension Specifications
Galvanised straight link welded chain.
Working load of 340 kg (750 lbs)
4.5 
Controls Specifications
Time switches, thermostats, etc. can be wired into the 
electrical supply. External controls supplied as an 
optional extra.