SECTION 4: Specifications 
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 
 
4.6 Linear Heater 
BH15
ST 
BH20
ST 
BH25
ST 
BH30
ST 
BH35
ST 
BH40
ST 
BH45
ST 
BH50
ST 
Input – kW 
15 
20 
25 
30 
35 
40 
45 
50 
Input – MJ 
54 
72 
90 
110 
125 
138 
162 
180 
Tube Length – mm 
6096 
9144 
9144 
12192 
12192 
12192 
15240 
15240 
Overall Heater Length - mm 
6661 
9709 
9709 
12757 
12757 
12757 
15815 
15815 
Weight – kg 
41 
55 
55 
68 
68 
68 
81 
81 
Heated Area – m
2
20-160 30-210 40-265  50-315 55-370 65-420 70-475 80-525 
Minimum Installation  
Height* – m 
2.5 2.5 3.0  3.5 4.6 5.0 5.0 5.0 
Recommended Installation 
Height* – m 
3.0 3.5 3.9  4.2 4.8 5.5 6.7 7.6 
 
 
4.8 U-Tube Heater 
BH15
U
BH20
U
BH25
U
BH30
U
BH35
U
BH40
U
BH45
U
BH50
U
Input – kW 
15 
20 
25 
30 
35 
40 
45 
50 
Input – MJ 
54 
72 
90 
110 
125 
138 
162 
180 
Tube Length – mm 
3323 
4843 
4843 
6363 
6363 
6363 
7998 
7998 
Overall Heater Length - mm 
3893 
5417 
5417 
6941 
6941 
6941 
8465 
8465 
Weight – kg 
39 
54 
54 
65 
65 
66 
96 
96 
Heated Area – m
2
20-160 30-210 40-265  50-315 55-370 65-420 70-475 80-525 
Minimum Installation  
Height* – m 
2.5 2.8 3.5  4.0 5.0 5.0 5.0 5.0 
Recommended Installation 
Height* – m 
3.0 3.5 3.9  4.2 4.8 5.5 6.7 7.6 
 
*Heights quoted are from ground level to bottom face of firing tube. 
 
 
NOTE:- 
Factory recommended mounting heights are listed above as a guideline. If infra-red heaters are 
mounted too low, they may result in heat discomfort. It is generally recommended to observe the 
recommended mounting heights to optimize comfort conditions. However, certain applications such as spot 
heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters being 
mounted outside of the factory recommended mounting heights. Clearances to combustibles must always be 
maintained.