Check all local codes for requirements, especially for the size and 
type of gas supply line required.
Note: Never use plastic pipe. Check to confirm whether your local 
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is 
always best to consult your local authority and installation code.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the 
unit. Where none exists, or where its size or location is not ad-
equate, contact your local authorized installer for installation or 
relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 
Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve  and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required 
by the National Fuel Gas Code that a drip line be installed near 
the gas inlet. This should consist of a vertical length of pipe tee 
connected into the gas line that is capped on the bottom in which 
condensation and foreign particles may collect. 
Figure 1
The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 
and Fittings
—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having jurisdiction. The state of Massachusetts requires that a flexible 
appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1.  To check the inlet pressure to the gas valve, a 1/8" (3.175mm) 
N.P.T. plugged tapping, accessible for test gauge connection,  
must  be  placed  immediately  upstream  of  the  gas  supply 
connection to the appliance.
2.  The  appliance  and  its  individual  shutoff  valve  must  be 
disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 1/2 
psig (3.5 kPa).
3.  The  appliance  must  be  isolated  from  the  gas  supply  piping 
system by closing its individual manual shutoff valve during 
any pressure testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig (3.5 kPa).
Attention!  If one of the procedures results in pressures in excess 
of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will 
result in a hazardous condition.
Checking Manifold Pressure
Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulator in the gas valve.  Natural gas models will have a manifold 
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet 
with the inlet pressure to the valve from a minimum of 4.5" w.c. 
(1.120kPa) for the purpose of input adjustment to a maximum of 
10.5" w.c. (2.614kPa)   Propane gas models will have a manifold 
pressure approximately 10.0"  w.c. (2.49kPa) at the valve outlet 
with the inlet pressure to the valve from a minimum of 11.0" w.c. 
(2.739kPa) for the purpose of input adjustment to a maximum of 
13.0" w.c. (3.237kPa).  
A 1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge 
connection, is located on the outlet side of the gas control.
GAS SUPPLY
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L 
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10 feet
0-3 meters
1/2”
12.7mm
3/8”
9.5mm
1/2”
12.7mm
3/8”
9.5mm
10-40 feet
4-12 meters
1/2”
12.7mm
1/2”
12.7mm
5/8”
15.9mm
1/2”
12.7mm
40-100 feet
13-30 meters
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
1/2”
12.7mm
100-150 feet
31-46 meters
3/4”
19mm
1/2”
12.7mm
7/8”
22.2mm
3/4”
19mm