Honeywell perfect climate comfort center control system Manuale Utente

Pagina di 44
68-0173—3
36
Heat Pump Recovery
In Mild Weather
When outdoor temperature is mild; for example 50°F (10°C), 
the recovery from energy savings is handled completely by 
the heat pump, without the need for auxiliary heat. The heat 
pump starts only after the setpoint has risen above the sensed 
temperature and is locked on until the comfort setpoint is 
reached. See Fig. 36.
Fig. 36. Adaptive Intelligent Recovery™ ramp for 
a heat pump in mild weather (50°F).
In Moderate Weather
When outdoor temperature is close to the balance point of the 
heat pump, the heat pump runs continuously during the 
recovery period and auxiliary heat cycles if necessary. 
See Fig. 37.
Fig. 37. Adaptive Intelligent Recovery™ ramp for 
a heat pump in moderate weather (20°F).
In Severe Weather
When the outdoor temperature is below the balance point of 
the heat pump, the heat pump and auxiliary heat run 
continuously in the recovery period. See Fig. 38.
Fig. 38. Adaptive Intelligent Recovery™ ramp for 
a heat pump in severe weather (0°F).
Comfort Period
In mild weather, the heat pump cycles continuously to 
maintain the sensed temperature within 1°F of the setpoint. In 
moderate weather, the heat pump cycles longer, minimizing 
the need for auxiliary heat. The heat pump runs the majority of 
the time in severe weather and only shuts off for brief periods 
using auxiliary heat to maintain temperature within 1°F of 
setpoint. See Fig. 36 through 38.
THERMAL PERFORMANCE
During severe weather, the PC8900A actually controls closer 
to the setpoint than a conventional control. This is because 
the heat anticipator is replaced by two electronic control 
strategies—cycling by heat anticipation and proportional plus 
integral (P+I) control.
Electronic cycling by heat anticipation acts like a traditional 
heat anticipator except that it never needs adjusting for 
various control circuit load currents. It cycles off the heating 
system slightly before the room temperature reaches the 
setpoint to keep heat that remains in the ductwork from 
overheating the room.
In severe weather, a conventional control with a heat 
anticipator tends to turn off the system too soon so the 
effective setpoint is somewhat below the setpoint. In very cold 
weather, the difference between setpoint and effective control 
point can be 5°F or 6°F (2°C or 3°C) with a conventional 
control. This phenomenon is called droop.
Proportional plus integral action eliminates droop by adjusting 
the on time of the stage until the control point matches the 
setpoint. The PC8900A maintains the space temperature 
within 1°F of the setpoint when the temperature has stabilized 
after an energy saving period.
This zero droop performance provides improved occupant 
comfort and energy savings. Occupants do not need to 
continually adjust thermostat settings to maintain desired 
temperature, even during severe weather.
Remote Communications
Adding the CM8900A Communications Module and the 
W8735B Telephone Access Module gives the PC8900A/
W8900A-C remote communications. Users are able to control 
current setpoint and system settings. They can monitor the 
WAKE
COMPRESSOR
SETPOINT
AUXILIARY
HEAT SETPOINT
COMPRESSOR:
AUXILIARY HEAT:
ON
OFF
ON
OFF
ROOM
TEMPERATURE
M6187
WAKE
COMPRESSOR
SETPOINT
AUXILIARY
HEAT SETPOINT
COMPRESSOR:
AUXILIARY HEAT:
ON
OFF
ON
OFF
ROOM
TEMPERATURE
M6188
WAKE
COMPRESSOR
SETPOINT
AUXILIARY
HEAT SETPOINT
COMPRESSOR:
AUXILIARY 
HEAT:
ON
OFF
ON
OFF
ROOM
TEMPERATURE
M6189