outdoor temperature, humidity, current setpoint, system mode, 
alarm out on High-Low temperature, filter status and 
equipment failure. See separate instructions on CM8900A 
and W88735B for more detailed information.
Minimum-Off Timing
A minimum-off timer in the Comfort Center™ control systeml 
assures that the cooling compressor or heat pump 
compressor does not come on again for at least five minutes 
after it turns off. The minimum-off timer is triggered when the 
compressor goes off and when the system switch is changed. 
If the compressor turns off when the setpoint is changed, then 
the minimum-off timer is triggered. The minimum-off timer 
operates during the first stage of cooling on the W8900A 
and C. The minimum-off timer operates during the first stage 
of both heating and cooling on the W8900B. The minimum-off 
timer can be disabled in the installer setup mode and can be 
overridden in the checkout mode.
Fan Control
The fan comes on when any of these conditions are present (it 
can take up to 20 seconds for the fan to turn on).
NOTES:
FAN ON: This setting means the fan runs 100 
percent of the time during this period.
FAN AUTO: The AUTO setting means the fan runs 
only with the heating or cooling system.
FAN CIRC: When the fan is set to CIRC, the fan runs 
at least 30 percent of the time, including the time the 
fan is on while the heating or cooling system is run-
ning. When the heating or cooling system is not 
running at all, the fan runs for ten minutes on, and 20 
minutes off. Protection against fan short cycling is 
built into the device.
The installer setup has the ability to extend fan operation 
following a cooling cycle. When selected, the fan run time at 
the end of a cooling cycle is extended 80 seconds.
Ventilation Control
When the Comfort Center™ program is configured for 
ventilation, the ventilator contacts are closed, activating high 
speed ventilation equipment in response to any of the 
following conditions:
• Ventilation request from the user.
• High CO
2
 condition (measured by CO
2
 monitor).
• High humidity condition while in the heating mode.
• Programming.
The ventilation control is set for a 20-second cycle so the user 
can wait up to 20 seconds for the ventilation to start after the 
request is made.
When the Comfort Center™ program is configured for no 
ventilation, the system fan is activated in response to a call for 
ventilation. When the Comfort Center™ system is configured 
for a VNT damper, calls for ventilation close the VNT damper 
contacts and activate the system fan.
NOTE: Each period can have a ventilation program.
Humidity Control (W8900A and B)
IMPORTANT
The humidity configuration can only be set for heat or 
cool by the installer. If configured for both, the 
Comfort Center™ control system ignores both set-
tings and no humidity control is activated.
Heat Mode
Heat humidification is activated when the sensed RH is below 
the setpoint RH and the fan is on. When a ventilator is 
installed and configured and the RH is above the setpoint, the 
Comfort Center™ program calls for ventilation to lower the 
humidity.
Cool Mode
Cool dehumidification is activated when the sensed RH is 
above the setpoint. This can cause overcooling; see W8900C 
Humidity Control section.
Dehumidification equipment can be controlled in many ways. 
See Installation section for hookup drawings.
Humidity Control with Fan
Select models of the W8900A-C can be configured to control 
humidity levels while the fan is energized. This type of 
humidity control does not require the heat output to be 
energized. In order for the humidity terminals (“HUM”) to 
energize, the following conditions must be met:
1. System switch must be in the heat mode or in Auto 
mode with heat being the last call.
2. There must be a call for humidity (sensed relative 
humidity [RH] is below RH setpoint).
3. Fan terminal (“G”) must be energized through program-
ming or by pressing the fan button on the PC8900A.
Frost Control
The frost Control needs an outdoor sensor to be activated. 
The Comfort Center™ control system calculates the 
possibility of condensation or frost forming by using the 
outside temperature and inside temperature to determine the 
dewpoint. When the dewpoint would cause frost or 
condensation, the humidification request will not be honored. 
The frost setting has a value range of zero to ten with zero 
representing glass with poor insulation and ten representing 
glass with perfect insulation.
NOTE: Set the frost setting to 10 to severely limit the frost 
control.
W8900C Humidity Control
The W8900C can be configured to control humidity levels in 
both the heat and cool modes. A humidifier is connected to 
the HUM terminals. The HUM contacts close and activate a 
humidifier when the sensor RH is below the setpoint RH. 
Dehumidification equipment is controlled by the Y1,Y2, and G 
terminals. These contacts close to activate the air conditioning 
equipment when the sensed RH is above the setpoint RH. 
The reheat feature is designed to keep the occupants 
comfortable. If the cooling setpoint is reached, but the 
dehumidification setpoint is not satisfied, the Comfort 
Center™ program turns on the heat. When the heat raises the 
temperature so there is a call for cooling and the