Mastic 91P Manuale Utente

Pagina di 42
16                                                                                                                                                       
L100001
                                                                                                                                                                            
17
�������
�������
������
�������
Figure 12 - Vent Opening Requirements 
Note: Horizontal runs of vent must 
be  supported  every  three  feet 
(914mm).  Use  wall  straps  for  this 
purpose. 
Figure 13 - Rigid Vent Pipe Connections
Female Locking Lugs 
Male Slots
REAR WALL VENT INSTALLATION 
When  installed  as  a  rear  vent  unit  this  appliance  may  be  vented  directly  to  a  termination  located  on  the  rear  wall  behind 
the appliance with 3' of vertical rise minimum.
•      The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See 
Figure 11.
•     
NOTE: A 30° elbow on 2 foot minimum vertical pipe is required for this configuration.
 
VENTING INSTALLATION   
1.    Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening. See Figure 11. 
     
Combustible  Walls:
  Cut  a  9
1
2
" H  x 
9
1
2
"  W 
(
241mm x 241mm
)  hole  through  the  exterior  wall 
and frame as shown. See Figure 12.
     
Noncombustible Walls:
 Hole opening should be 
7
1
2
" (190mm) in diameter.
2.  Rigid vent pipes and fittings have special twist-lock 
connections. Assemble the desired combination of 
pipe and elbows to the appliance adaptor with pipe 
seams oriented towards the wall or floor.
 
Twist-lock Procedure:
 The female ends of the pipes 
and fittings have three locking lugs (indentations). 
These lugs will slide straight into matching slots on 
the male end of adjacent pipes and fittings. Push 
the  pipe  sections  together  and  twist  one  section 
clockwise approximately one-quarter turn until the 
sections are fully locked. See Figure 13.
3.  Attach vent pipe assembly to the fireplace. Set fire-
place in front of its permanent location to insure 
minimum clearances. Mark the wall for a 
9
1
2
"H 
9
1
2
"W  (
241mm x 241 mm
) rectangle  hole  (for 
noncombustible material such as masonry block or 
concrete, a 7
1
/
2
" [190mm] diameter hole is accept-
able). See Figure 11. The center of the hole should 
line up with the center line of the horizontal rigid 
vent pipe end. Be sure to allow for minimum rise. Cut a 
9
1
/
2
"x
9
1
/
2
" (
241mm X 241mm
) rectangle hole through combustible 
exterior wall (7
1
/
2
" [190mm] diameter hole if noncombustible). Frame as necessary. Allow 
1
/
4
" minimum rise per foot. See 
Figure 12.
Figure 11 - Rear Vent Application,
Maximum Horizontal Distance 
Maximum
      20"