FieldServer FS-8700-64 Manuale Utente

Pagina di 22
FS-8700-64 
ATMI 
ACM 
       Page 
of 
22 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com
 
 
Example 
 
//    Data Arrays 
// 
Data_Arrays 
Data_Array_Name,  
Data_Format,   Data_Array_Length 
DA_AI_01,         
UInt16,       
200 
DA_AO_01,         
UInt16,       
200 
DA_DI_01,         
Bit,          
200 
DA_DO_01,         
Bit,          
200
 
 
 
4.2  Client Side Connections 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is 
connected to the FieldServer 
P1-P8, R1-R2 
Baud* 
Specify baud rate 
110 – 115200, standard baud 
rates only 
Parity* 
Specify parity 
Even, Odd, None, Mark, Space 
Data_Bits* 
Specify data bits 
7, 8 
Stop_Bits* 
Specify stop bits 
Protocol 
Specify protocol used 
ATMI 
Handshaking* 
Specify hardware handshaking 
RTS, RTS/CTS, None 
Poll Delay* 
Time between internal polls 
0-32000 seconds 
default 1 second 
Timeout 
Specifies the amount of time that 
may pass between complete 
data screens. If this time expires 
a timeout error is produced but 
the processing of data is not 
affected. The port is not cleared 
and gas data is not reset. 
This value should provide a 
margin over the time configured 
between samples in the 
CONFIG.DAT profile of the 
ACM unit. 
IC_Timeout 
This parameter is used in a way 
that is different to most 
FieldServer driver applications. 
In this case of this driver it 
specifies the maximum amount 
of time that may pass between 
the driver receiving an incoming 
character. If the time is 
exceeded then an error is 
produced but note that the error  
has no other effect on the driver. 
The port is not cleared and gas 
data is not reset. 
This value (specified in 
seconds) should be set allow a 
margin between time stamp 
messages from the ACM unit.