4.4.2  Driver Specific Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name of Node to fetch data 
from 
One of the node names 
specified in “Client Node 
Descriptor” above 
Data_Array_Offset 
Position in the data array to 
which data should start being 
written. 
0, 1 , 2 , 3 
Length 
Length of Map Descriptor. The 
length is required to help the 
driver validate the CSV file. 
 
Set the length to a multiple of 
16. The multiple should be the 
maximum area number. 
1 – 1280 
Address 
Starting address of read block 
 
Driver specific keywords 
 
The following parameters apply only to the AMI ACM driver. 
 
ATMI_Data* 
Used to specify which 
component of the gas data 
structure to store. 
 
You will need one map 
descriptor for each 
component that you are 
interested in storing. 
 
See section 6.9 for more 
info. 
 
 
Slot-alarm, 
Slot-warning, 
Slot-combo 
Slot-values 
Port-alarm, 
Port-warning, 
Port-combo 
Gas-value, (== Port-values) 
Current-Port 
Current-Slot 
Malfunctions 
 
 
4.4.3 Timing 
Parameters 
Column Title 
Function 
Legal Values 
Scan_Interval 
Rate at which data is polled 
>0.1s