Example  
The following FieldServer settings are suitable for default ACM settings. 
 
//    Client Side Connections 
 
Connections 
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay 
P8,   9600, None,   ATMI    , None,     0.100s 
 
 
4.3  Client Side Nodes 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
ACM units do not have a 
node ID contained in the 
serial data. This field s not 
used in the ATMI ACM 
driver. 
 
Protocol 
Specify protocol used 
ATMI 
Port 
Specify which port the 
device is connected to the 
FieldServer 
P1-P8, R1-R2 
 
Example 
 
//    Client Side Nodes 
 
Nodes 
Node_Name, Protocol, Port 
ACM-1    , ATMI    , P8
 
 
 
4.4  Client Side Map Descriptors 
4.4.1  FieldServer Specific Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Map_Descriptor_Name 
Name of this Map Descriptor  Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array where 
data is to be stored in the 
FieldServer 
One of the Data Array 
names from “Data Array” 
section above 
Data_Array_Location 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
PASSIVE