4.4.4  Map Descriptor Example 1- Gas Values, Alarms & Warnings for all slots/ports. 
This example illustrates the map descriptors required to complete store ACM data for 80 areas. Each map descriptor tells the ATMI ACM driver 
where to store each component of ACM data. The gas number & area number determine the position in the array. Read section 6.1 for more 
information 
 
Map_blocks 
Map_block_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, protocol, atmi_data 
MAP1                  , DATA1_1              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  port-values 
MAP2                  , DATA1_2              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  port-alarm 
MAP3                  , DATA1_3              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  port-warning 
MAP4                  , DATA1_4              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  slot-alarm 
MAP5                  , DATA1_5              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  slot-warning
 
MAP6                  , DATA1_6              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  slot-combo 
MAP7                  , DATA1_7              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  port-combo
 
MAP8                  , DATA1_8              , 0                             , passive   , ACM1       , 0,       1280       , ATMI    ,  slot-values
 
A different array is 
used for each 
atmi_data 
component being 
stored. 
 
The gas value array 
would typically be 
an array of FLOATs 
and the alarms and 
warnings could be 
any data type 
including bit arrays
 
This is a passive 
client driver so the 
function must be 
passive. 
 
 
This node name will 
connect this map 
descriptor to a node 
which in turn  is 
connected to a port. 
Hence the map 
descriptor is 
connected to a port.
These keywords tell the driver which component of the 
ACM data should be 
Stored using each map descriptor. 
 
If you were only interested in the current value then 
you would only use one map descriptor and set the 
atmi_data parameter equal to gas-value 
 
The “…-combo” types store a 1 for an alarm OR 
warning and a zero when neither conditionis present.