Configuring the FieldServer as a Setra Model 370 Digital Pressure Gage 
Client 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer 
Configuration Manual.  The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a Setra Model 370 Digital Pressure Gage. 
4.1. Data 
Arrays/Descriptors 
The configuration file tells the FieldServer about its interfaces, and the routing of data 
required. In order to enable the FieldServer for Setra Model 370 Digital Pressure Gage 
communications, the driver independent FieldServer buffers need to be declared in the 
“Data Arrays” section, the destination device addresses need to be declared in the “Client 
Side Nodes” section, and the data required from the Servers needs to be mapped in the 
“Client Side Map Descriptors” section.  Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the 
default. 
Section Title 
Data_Arrays 
Column Title 
Function 
Legal Values 
Data_Array_Name 
Provide name for Data Array 
Up to 15 alphanumeric 
characters 
Data_Array_Format 
Provide data format. Each Data Array can 
only take on one format. 
For this driver, FieldServer recommends 
the use of a FLOAT Data Array. This is 
because the pressure and status settings 
are reported as real signed numbers with 
some significant digits after the decimal 
point. 
Float, Bit, UInt16, 
SInt16, Packed_Bit, 
Byte, Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number of Data Objects. Must be larger 
than the data storage area required by the 
Map Descriptors for the data being placed 
in this array. 
1-10,000 
 
Example 
 
//    Data Arrays 
 
 
Data_Arrays 
 
 
Data_Array_Name, 
Data_Format, 
Data_Array_Length, 
DA_PRESSURE, 
FLOAT, 
200 
DA_STATUS, 
FLOAT, 
200 
DA_DI_01, 
Bit, 
200 
DA_DO_01, 
Bit, 
200