FS-8700-101_Setra Model 370 Digital Pressure Gage Manual   
 
Page 9 of 23 
 
 
FieldServer Technologies
 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel
: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
4.4. 
Client Side Map Descriptors 
4.4.1. FieldServer 
Related 
Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Map_Descriptor_Name  Name of this Map Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array where 
data is to be stored in the 
FieldServer 
One of the Data Array names 
from “Data Array” section 
above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC 
4.4.2. 
Driver Related Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name of Node to fetch data 
from 
One of the node names specified in 
“Client Node Descriptor” above 
Data_Type 
This commonly used 
parameter has no special 
meaning to this driver and 
may be omitted. 
Register, Coil, AI, DI 
Length 
Length of Map Descriptor 
The driver knows the correct length 
for the various Map Descriptors and 
will prompt you accordingly if an 
invalid length is specified. 
Pressure : Set Length 5 
Status: Set Length 14 
Verification Info: Set length 100. 
Address 
This commonly used parameter has no special meaning to this 
driver and may be omitted. 
Gage_Function* 
Specifies what data should 
be read and stored. 
 
If you omit this parameter 
then the driver assumes 
you are reading pressure. 
Pressure
, Status, Verify 
4.4.3. Timing 
Parameters 
Column Title 
Function 
Legal Values 
Scan_Interval 
Rate at which data is polled 
≥0.001s