FieldServer FS-8700-101 Manuale Utente

Pagina di 23
FS-8700-101_Setra Model 370 Digital Pressure Gage Manual   
 
Page 8 of 23 
 
 
FieldServer Technologies
 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel
: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
4.2. 
Client Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is 
connected to the FieldServer 
P1-P8, R1-R2
1
 
Protocol 
Specify protocol used 
Setra370 
Baud* 
Specify baud rate 
110 – 115200, standard baud 
rates only, 2400
Parity* 
Specify parity 
Even, Odd, None, Mark, Space
Data_Bits* 
Specify data bits 
7, 8 
Stop_Bits* 
Specify stop bits 
Handshaking* 
Specify hardware handshaking 
 
The Setra Model 370 does not support 
handshaking. 
RTS, RTS/CTS, None 
Poll _Delay* 
Time between internal polls 
0-32000 seconds, 1 second 
 
Example 
 
//    Client Side Connections 
 
Connections 
Port, 
Protocol, 
Baud,  Parity, 
Handshaking, 
Poll_Delay 
P8, 
Setra370, 
2400, 
None, 
None, 
0.100s 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
This commonly used parameter has no meaning for this driver and may be 
omitted. 
Protocol 
Specify protocol used 
Setra370. 
Connection 
Specify which port the device is connected 
to the FieldServer 
P1-P8, R1-R2
1
 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Protocol, 
Connection 
 
Gage1, 
Setra370, 
P8 
 
                                                 
1
 
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction 
manual for details of the ports available on specific hardware.