Modbus Read, Write and Override Parameters plus Exception Codes 
198 
UDC2500 Universal Digital Controller Product Manual 
4/07 
10.7.2 SP 
Ramp/Rate/Program 
Table 10-10  Set-up Group – Setpoint Ramp/Rate 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access 
Data Range or 
Enumerated Selection 
 
Hex 
Decimal 
 
 
 
SP Ramp 
0096 150 
INT  R/W 
Disabled 
1 = Enabled 
Single SP Ramp 
Time 
19 
25 
FP 
R/W 
0 to 255 (minutes) 
Final Ramp SP 
Value 
001A 
026 
FP 
R/W 
PV Range in Engineering 
Units 
SP Rate 
F0 240 
INT 
R/W  0 
Disabled 
1 = Enabled 
Rate Up (EU/HR)  006C 
108 
FP 
R/W 
0 to 9999 
Rate Down 
(EU/HR) 
006D 
109 
FP 
R/W 
0 to 9999 
Setpoint 
Program  
00B2 178 
INT  R/W 
Disabled 
1 = Enabled 
Start Segment # 
58 
88 
FP 
R/W 
1 to 12 
End Segment 
#(Soak) 
00B0 
176 
INT 
R/W 
0 = Soak 2 
1 = Soak 4 
2 = Soak 6 
3 = Soak 8 
4 = Soak 10 
5 = Soak 12 
Engineering Units 
or Ramp 
Segments 
00B6 
182 
INT 
R/W 
0 = HRS:MIN 
1 = Degrees/Minute 
2 = EU/Hour 
Program Recycles  59 
89 
FP 
R/W 
0 to 100 
Guaranteed Soak 
Deviation 
0057 
087 
FP 
R/W 
0 to 99.9 (0 = no soak) 
Program End 
State 
00B5 
181 
INT 
R/W 
0 = Disable SP  Program 
1 = Hold at Program End