Modbus Read, Write and Override Parameters plus Exception Codes
4/07
UDC2500 Universal Digital Controller Product Manual
199
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Controller Status
at Program End
at Program End
00B4
180
INT
R/W
0 = Last Setpoint and Mode
1 = Manual, Failsafe Output
Reset SP Program
(ToBEGIN)
(ToBEGIN)
00B3
179
INT
R/W
0 = Disable
1 = Via Keypad
1 = Via Keypad
PV Hotstart
00E2
226
INT
R/W
0 = Disabled
1 = Enabled
1 = Enabled
Segment #1 Ramp
Time
Time
0039
057
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
or
0 to 999 (Degrees/Minute)
Segment #2 Soak
Setpoint Value
Setpoint Value
003A
058
FP
R/W
Within Setpoint Limits
Segment #2 Soak
Time
Time
003B
059
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #3 Ramp
Time
Time
003C
060
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
or
0 to 999 (Degrees/Minute)
Segment #4 Soak
Setpoint Value
Setpoint Value
003D
061
FP
R/W
Within Setpoint Limits
Segment #4 Soak
Time
Time
003E
062
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #5 Ramp
Time
Time
003F
063
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
or
0 to 999 (Degrees/Minute)
Segment #6 Soak
Setpoint Value
Setpoint Value
0040
064
FP
R/W
Within Setpoint Limits
Segment #6 Soak
Time
Time
0041
065
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #7 Ramp
Time
Time
0042
066
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
or
0 to 999 (Degrees/Minute)
Segment #8 Soak
Setpoint Value
Setpoint Value
0043
067
FP
R/W
Within Setpoint Limits