Honeywell UDC2500 Manuale Utente

Pagina di 243
Modbus Read, Write and Override Parameters plus Exception Codes 
200 
UDC2500 Universal Digital Controller Product Manual 
4/07 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access 
Data Range or 
Enumerated Selection 
 
Hex 
Decimal 
 
 
 
Segment #8 Soak 
Time 
0044 
068 
FP 
R/W 
99.59 (0-99 Hrs:0-59 Min) 
Segment #9 Ramp 
Time 
0045 
069 
FP 
R/W 
99.59 (0-99 Hrs:0-59 Min)  
or  
0 to 999 (Degrees/Minute) 
Segment #10 
Soak Setpoint 
Value 
0046 
070 
FP 
R/W 
Within Setpoint Limits 
Segment #10 
Soak Time 
0047 
071 
FP 
R/W 
99.59 (0-99 Hrs:0-59 Min) 
Segment #11 
Ramp Time 
0048 
072 
FP 
R/W 
99.59 (0-99 Hrs:0-59 Min)  
or  
0 to 999 (Degrees/Minute) 
Segment #12 
Soak Setpoint 
Value 
0049 
073 
FP 
R/W 
Within Setpoint Limits 
Segment #12 
Soak Time 
004A 
074 
FP 
R/W 
99.59 (0-99 Hrs:0-59 Min)