Configuring SDSL Frame Alarm Profiles
 
114
Avidia System Configuration and Management User Manual
C
ONFIGURING
 SDSL F
RAME
 A
LARM
 P
ROFILES
SDSL frame alarm profiles determine the conditions that generate SNMP traps. When the 
configured thresholds are met or exceeded, the SNMP agent sends a trap to the configured trap 
receiver(s). Only one trap is sent for each 15-minute data collection period. SDSL frame port 
configuration requires assigning an alarm profile, therefore you must configure the desired 
alarm profile prior to configuring the SDSL frame port. A default profile exists with an index 
of 1. You cannot delete the default profile.
You configure SDSL frame alarm profiles from the 
::alarm=>
 prompt. From the 
::root=>
 
prompt, type the following command then press 
 to display the 
::alarm=>
 prompt.
configuration sdsl frame profile alarm
Adding SDSL Frame Alarm Profiles
From the 
::alarm=>
 prompt, type the new command in the following format then press 
 to create a new SDSL frame alarm profile. The profile is automatically assigned the next 
available index number in the SDSL frame alarm profile table.
new <loswmode> <mgn> <mgnmode> <es> <esmode> <uas> <uasmode>
Parameters
<loswmode>
Loss of Sync Word alarm setting. A Loss of Sync Word alarm occurs when one of the 
SDSL frame loops is out of sync. Type 
enable
 or 
disable
<mgn>
The margin threshold value, in decibels. When the margin falls below the specified 
threshold, the margin alarm is activated. A typical margin threshold value is 6.
<mgnmode>
The margin alarm setting. Type 
enable
 or 
disable
.
<es>
The errored seconds threshold. When the number of errored seconds in the current 
15-minute data collection interval exceeds the specified threshold, the errored seconds 
alarm is activated. Errored seconds are seconds during which errors occur that prevent the 
payload from being corrected. A typical errored second threshold value is 17.
ENTER
ENTER