Hardware and Connectivity  49
Powering up your IOLAN
Wiring up an HV unit
NOTES:
1. 
For terminal# 1 through 6, the use of ring terminals size #6 (M3.5) is recommended using stranded wire size AWG 
18-14. Tighten all screws to a torque of 12 Lb-in (1.36 Nm).
2. 
For terminal# E, the use of ring terminal size #8 (M4) is recommended using stranded wire size AWG 18-14. 
Tighten screw to a torque of 12 Lb-in (1.36 Nm).
3. 
Use the “Chassis Ground” terminal connection for grounding the unit. “Earth Ground” should be used as secondary 
grounding source only.
4. 
Be sure to replace the clear plastic electrical safety shield before applying power to the unit.
Terminal # Description
Usage
1
Normally Open Normally Open is a fail-safe relay connection. Use this with the 
Common terminal to act as switch contacts that remain open when 
the unit is powered off or in a failure state.
2
Common
Common is a fail-safe relay connection. Use this terminal in 
conjunction with the Normally Open or Normally Closed terminals.
3
Normally 
Closed
Normally Closed is a fail-safe relay connection. Use this with the 
Common terminal to act as switch contacts that remain closed 
when the unit is powered off or in a failure state.
4
+ / L 
+ / L is connected to the positive (+) input for DC sources or to the 
Live input for AC sources. Use with partner terminal -/N.
5
- / N
- / N is connected to the negative (-) input for DC sources or to the 
Neutral input for AC sources. Use with partner terminal +/L.
6
Chassis Ground Chassis Ground must be connected to "Equipment Ground" for DC 
installations or "Safety Ground" for AC installations.
E
Earth Ground
Earth Ground is a connection to the chassis that can be used for 
earth bonding.