Black Box LES1216A-R2 Manuale Utente

Pagina di 286
 
 
Logging  
 
 
 
 
Enabled 
Log interval 
 
 
 
 
600 second 
Number of power outlets 
 
 
4   (depends on the type/model of the RPC) 
 
# config -s config.ports.port2.power.type=APC 7900 
# config -s config.ports.port2.power.name=MyRPC 
# config -s "config.ports.port2.power.description=RPC in room 5" 
# config -s config.ports.port2.power.username=rpclogin 
# config -s config.ports.port2.power.password=secret 
# config -s config.ports.port2.power.snmp.community=v1 
# config -s config.ports.port2.power.log.enabled=on 
# config -s config.ports.port2.power.log.interval=600 
# config -s config.ports.port2.power.outlets=4 
The following five commands are used by the  Management Console to add the RPC to “Managed 
Devices”: 
# config -s config.devices.device3.connections.connection1.name=myRPC 
# config -s "config.devices.device3.connections.connection1.type=RPC Unit" 
# config -s config.devices.device3.name=myRPC 
# config -s "config.devices.device3.description=RPC in room 5" 
# config -s config.devices.total=3 
The following command will synchronize the live system with the new configuration: 
# config -a 
14.11 Environmental 
To configure an environmental monitor with the following details: 
 
Monitor name   
 
Envi4 
Monitor Description 
 
Monitor in room 5 
Temperature offset 
 
Humidity offset  
 
Enable alarm 1 ? 
 
yes 
Alarm 1 label   
 
door alarm 
Enable alarm 2 ? 
 
yes 
Alarm 2 label   
 
window alarm   
Logging enabled ? 
 
yes 
Log interval 
 
 
120 seconds 
 
# config -s config.ports.port3.enviro.name=Envi4 
# config -s "config.ports.port3.enviro.description=Monitor in room 5" 
# config -s config.ports.port3.enviro.offsets.temp=2 
# config -s config.ports.port3.enviro.offsets.humid=5 
# config -s config.ports.port3.enviro.alarms.alarm1.alarmstate=on 
# config -s config.ports.port3.enviro.alarms.alarm1.label=door alarm 
# config -s config.ports.port3.enviro.alarms.alarm2.alarmstate=on 
# config -s config.ports.port3.enviro.alarms.alarm2.label=window alarm 
# config -s config.ports.port3.enviro.alarms.total=2 
# config -s config.ports.port3.enviro.log.enabled=on 
# config -s config.ports.port3.enviro.log.interval=120 
Assign alarms.total=2 even if they are off.  
The following 5 commands will add the environmental monitor to “Managed devices”: 
_____________________________________________________________________ 
 
 
724-746-5500 | blackbox.com
 