# config -s config.cascade.slaves.slave1.address=192.168.0.153 
# config -s "config.cascade.slaves.slave1.description=CM in office 42" 
# config -s config.cascade.slaves.slave1.label=les1116-5 
# config -s config.cascade.slaves.slave1.ports=16 
 The total number of slaves must also be incremented. If this is the first slave you’re adding, type: 
# config -s config.cascade.slaves.total=1 
Increment this value when adding more slaves. 
NOTE: If a slave is added using the CLI, then the master SSH public key will need to be manually copied 
to every slave device before cascaded ports will work (refer Chapter 4). 
The following command will synchronize the live system with the new configuration: 
# config -r cascade 
14.9  UPS Connections 
Managed UPSes 
Before adding a managed UPS, make sure that at least 1 port has been configured to run in 'device 
mode', and that the device is set to 'ups'. 
To add a managed UPS with the following values: 
Connected via   
 
 
 
Port 1 
UPS name 
 
 
 
 
My UPS 
Description 
 
 
 
 
UPS in room 5 
Username to connect to UPS   
 
User2 
Password to connect to UPS 
 
 
secret 
shutdown order  
 
 
 
2   (0 shuts down first) 
Driver   
 
 
 
 
genericups 
Driver option - option   
 
 
option 
Driver option - argument 
 
 
argument 
Logging  
 
 
 
 
Enabled 
Log interval 
 
 
 
 
2 minutes 
Run script when power is critical 
 
Enabled 
 
# config -s config.ups.monitors.monitor1.port=/dev/port01           
If the port number is higher than 9, eg port 13, enter: 
# config -s config.ups.monitors.monitor1.port=/dev/port13 
 
 
# config -s "config.ups.monitors.monitor1.name=My UPS" 
# config -s "config.ups.monitors.monitor1.description=UPS in room 5" 
# config -s config.ups.monitors.monitor1.username=User2 
# config -s config.ups.monitors.monitor1.password=secret 
# config -s config.ups.monitors.monitor1.sdorder=2 
# config -s config.ups.monitors.monitor1.driver=genericups 
# config -s config.ups.monitors.monitor1.options.option1.opt=option 
# config -s config.ups.monitors.monitor1.options.option1.arg=argument 
# config -s config.ups.monitors.monitor1.options.total=1 
# config -s config.ups.monitors.monitor1.log.enabled=on 
# config -s config.ups.monitors.monitor1.log.interval=2 
# config -s config.ups.monitors.monitor1.script.enabled=on 