Make sure to increment the total monitors: 
# config -s config.ups.monitors.total=1 
The  five  commands below will add the UPS to Managed devices. Assuming there are already  two 
managed devices configured: 
# config -s "config.devices.device3.connections.connection1.name=My UPS" 
# config -s "config.devices.device3.connections.connection1.type=UPS Unit" 
# config -s "config.devices.device3.name=My UPS" 
# config -s "config.devices.device3.description=UPS in toom 5" 
# config -s config.devices.total=3 
To delete this managed UPS: 
# config -d config.ups.monitors.monitor1 
 
Decrement monitors.total when deleting a managed UPS. 
Remote UPSes 
To add a remote UPS with the following details (assuming this is our first remote UPS): 
UPS name 
 
 
oldUPS 
Description 
 
 
UPS in room 2 
Address  
 
 
192.168.50.50 
Log status 
 
 
Disabled 
Log rate 
 
 
240 seconds 
Run shutdown script   
Enabled 
 
# config -s config.ups.remotes.remote1.name=oldUPS  
# config -s "config.ups.remotes.remote1.description=UPS in room 2" 
# config -s config.ups.remotes.remote1.address=192.168.50.50 
# config -d config.ups.remotes.remote1.log.enabled 
# config -s config.ups.remotes.remote1.log.interval=240 
# config -s config.ups.remotes.remote1.script.enabled=on 
# config -s config.ups.remotes.total=1 
The following command will synchronize the live system with the new configuration: 
# config -a 
14.10 RPC Connections 
You can add  an RPC connection  from the command line. We do not recommend that you do this 
because of dependency issues. 
 
However FYI before adding an RPC the Management Console GUI code makes sure that at least one port 
has been configured to run in 'device mode', and that the device is set to 'rpc'. 
To add an RPC with the following values: 
 
RPC type 
 
 
 
 
APC 7900 
Connected via   
 
 
 
Port 2 
UPS name 
 
 
 
 
MyRPC 
Description 
 
 
 
 
RPC in room 5 
Login name for device   
 
 
rpclogin 
Login password for device 
 
 
secret 
SNMP community 
 
 
 