IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after 
the equipment is serviced.
IMPORTANT
1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture 
quickly. Therefore it is important to prevent moisture from entering the system 
when replacing or servicing parts.
2. Always install a new drier every time the sealed refrigeration system is 
opened.
3. Do not leave the system open for longer than 15 minutes when replacing or 
servicing parts.
A. Service for Refrigerant Lines
1. Refrigerant Recovery 
The icemaker unit is provided with refrigerant access valves. Using proper refrigerant 
practices recover the refrigerant from the access valves and store it in an approved 
container. Do not discharge the refrigerant into the atmosphere.
2. Evacuation and Recharge [R-404A]
1)  Attach service manifold hoses and a vacuum pump to the system. Be sure to connect 
charging hoses to both high-side and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current 
refrigerants. However, the rubber hose and gauge manifold to be used for 
evacuation and refrigerant charge should be exclusively for POE oils.
2)  Turn on the vacuum pump. Never allow the oil in the vacuum pump to flow backward.
3)  Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends 
on pump capacity.
4)  Close the low-side valve and high-side valve on the service manifold.
5)  Disconnect the vacuum pump, and attach a refrigerant service cylinder to the high-
side line. Remember to loosen the connection, and purge the air from the hose. See 
the nameplate for the required refrigerant charge. Hoshizaki recommends only virgin 
refrigerant or reclaimed refrigerant which meets ARI Standard No. 700-88 be used.
6)  A liquid charge is recommended for charging an R-404A system. Invert the service 
cylinder and place it on scales. Open the high-side, service manifold valve. 
7) Allow the system to charge with liquid until the proper charge weight is met.
8)  If necessary, add any remaining charge to the system through the low-side. Use a 
throttling valve or liquid dispensing device to add the remaining liquid charge through