If airflow through the equipment rack and the devices that occupy it is blocked or 
restricted, or if the ambient air drawn into the rack is too warm, an over-
temperature condition within the rack and the devices that occupy it can occur. 
The site should also be as dust-free as possible. Dust tends to clog the server 
fans, reducing the flow of cooling air through the equipment rack and the devices 
that occupy it. This reduction increases the risk of an over-temperature condition. 
Additionally, the following guidelines will help you plan your equipment rack 
configuration: 
  Besides airflow, you must allow clearance around the rack for maintenance. 
  When mounting a device in an open rack, ensure that the rack frame does 
not block the front intakes or the rear exhausts. 
Temperature and Humidity Guidelines 
Table 9 lists the operating and non-operating environmental site requirements for 
the SV Director Server. The server normally operates within the ranges listed; 
however, if a temperature measurement approaching a minimum or maximum 
parameter indicates a potential problem. Maintain normal operation by 
anticipating and correcting environmental anomalies before they approach 
critical values by properly planning and preparing your site before you install the 
server. 
Warning! To prevent the system from overheating, do not operate it in an area 
that exceeds the maximum recommended ambient temperature of: 95°F (35°C). 
Statement 1047 
Table 9. 
Operating and Nonoperating Environmental Specifications 
Specification 
Minimum 
Maximum 
Temperature, ambient operating 
50°F (10°C) 
95°F (35°C) 
Temperature, ambient nonoperating and storage 
-40°F (°C) 
158°F (70°C) 
Humidity, ambient (noncondensing) operating 
5% 
85% 
Humidity, ambient (noncondensing) 
nonoperating and storage 
50% 
90% 
Vibration, operating 
5
–500 Hz, 2.20 g RMS random 
— 
Power Considerations 
For redundancy, you need to configure the SV Director Server with two AC-input 
power supplies. For power supply pinout descriptions, see the 
The AC power supplies are hot-swappable.  
Warning! Blank faceplates and cover panels serve three important functions: 
they prevent exposure to hazardous voltages and currents inside the chassis; 
they contain electromagnetic interference (EMI) that might disrupt other 
equipment; and they direct the flow of cooling air through the chassis. Do not 
operate the system unless all cards, faceplates, front covers, and rear covers are 
in place. Statement 1029