8.1.5 Alarm relay
With oAx=ALr the AUX relay operates as alarm relay. It is activated every time an alarm happens. Its
status depends on the tbA parameter: if tbA=Y, the relay is silenced by pressing any key.
If tbA=n, the alarm relay stay on until the alarm condition recovers.
If tbA=n, the alarm relay stay on until the alarm condition recovers.
8.1.6 Activation during energy saving cycles
With oAx=HES, the AUX relay is energised when the energy saving cycle is activated.
9
FRONT PANEL COMMANDS
Press to display target set point and the real set point. When in programming mode
it selects a parameter or confirms an operation
(ECO) To switch on and off the Energy Saving mode or the light output. Other
functions related to par. LGC and LG2
functions related to par. LGC and LG2
(UP) In programming mode it browses the parameter codes or increases the
displayed value. Other functions related to par. UPC and UP2
displayed value. Other functions related to par. UPC and UP2
(DOWN) In programming mode it browses the parameter codes or decreases the
displayed value. Other functions related to the par. dnC and dn2
(ONOFF) Keep it pressed for 3 sec to switch on and off the device
KEYS COMBINATION
+
To lock or unlock the keyboard
+
To enter in programming mode
+
To return to room temperature display
ICON
MODE
MEANING
On
Compressor enabled
Flashing
Anti-short cycle delay enabled (AC parameter)
On
Light output enabled
On
Ventilator output enabled
Flashing
Ventilator delay after defrost
,
On
Measurement unit
Flashing
Programming mode
On
Energy saving mode active
On
An alarm condition is present
Flashing
Start-up operations are pending
On
Auxiliary output is activated
NOTE: start-up operations lasts about 30 sec after powering on the device. At the end of this phase,
the alarm icon will switch off if no alarm is active.
the alarm icon will switch off if no alarm is active.
9.1
SET POINT MENU
The SET key gives access to a quick menu where it is possible to see:
-
the set point value
-
the real set point value (rSE)
Push and release the SET key five times or wait for 60 sec to return to normal visualisation.
9.2
CHANGE THE SETPOINT
1.
Push the SET key for more than 2 sec to change the Set point value;
2.
The value of the set point will be displayed and the “°C” LED starts blinking;
3.
To change the Set value push the UP or DOWN button.
4.
To memorise the new set point value push the SET key again or wait for 60 sec.
9.3
START A MANUAL DEFROST
Push the DEFROST button for more than 2 sec to start a manual defrost.
9.4
CHANGE A PARAMETER VALUE
To change the parameter values operate as follows:
1. Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec (“°C” LED starts
blinking).
2. Select the required parameter. Press the SET button to display its value
3. Use UP or DOWN buttons to change its value.
3. Use UP or DOWN buttons to change its value.
4. Press SET to store the new value and move to the following parameter.
To exit: Press SET+UP buttons or waits for 15 sec without pressing any key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
9.5
ENTERING THE HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing SET+DOWN buttons for 3 sec (“°C” or “°F” LED starts
ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing SET+DOWN buttons for 3 sec (“°C” or “°F” LED starts
blinking).
2. Released the keys and then push again SET+DOWN buttons for more than 7 sec. The “L2” label
will be displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the SET key to display its value
5. Use
5. Use
UP
or DOWN to change its value.
6. Press SET to store the new value and move to the following parameter.
To exit: Press SET+
UP
or wait for 15 sec without pressing any key.
NOTE1: if there are no parameters in L1, after 3 sec the “nP” label will be displayed. Keep the keys
pushed till the “L2” message will be displayed.
NOTE2: the previous set value will be stored even if the programming mode is exited by waiting for the
time-out to expire.
MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user
time-out to expire.
MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user
level) by pressing SET+DOWN. If a parameter is visible also in the First Level, in the HIDDEN MENU
the decimal point will be lit.
the decimal point will be lit.
9.6
LOCK THE KEYBOARD
1.
Keep both UP and DOWN buttons pressed for more than 3 sec.
2.
The “oFF” label will be displayed and the keyboard will be locked. If any button is pressed more
than 3 sec, the “oFF” message will be displayed.
than 3 sec, the “oFF” message will be displayed.
9.7
UNLOCK THE KEYBOARD
Keep both UP and DOWN buttons pressed together for more than 3 sec till the “on” message will be
displayed.
displayed.
9.8
THE ON/OFF FUNCTION
If onF = oFF, the instrument will be switched off by pushing the ON/OFF button. The
“OFF” message will appear on the display. In this configuration the regulation is
disabled. To switch the instrument on, push again the ON/OFF button.
disabled. To switch the instrument on, push again the ON/OFF button.
WARNING: any load connected to the normally closed contacts of the relays is always supplied
from the main voltage, even if the instrument is in standby mode.
10 PARAMETERS
REGULATION
Set
Regulation Set Point: LS to US
LS
Minimum SET POINT: (-55.0°C to SET; -67°F to SET) sets the minimum value for the set
point.
point.
US
Maximum SET POINT: (SET to 150.0°C; SET to 302°F) set the maximum value for set point.
HY
Differential in normal mode (energy saving mode not active): (0.1 to 25.0°C; 1 to 45°F)
differential for set point. Compressor Cut-IN is
[SET-POINT + HY]. Compressor Cut-OUT is when the temperature reaches the set point.
differential for set point. Compressor Cut-IN is
[SET-POINT + HY]. Compressor Cut-OUT is when the temperature reaches the set point.
HYE
Differential when energy saving mode is active: (0.1 to 25.0°C; 1 to 45°F) differential for set
point. Compressor Cut-IN is [SET-POINT + HES + HYE]. Compressor Cut-OUT is when the
temperature reaches the [SET-POINT + HES].
point. Compressor Cut-IN is [SET-POINT + HES + HYE]. Compressor Cut-OUT is when the
temperature reaches the [SET-POINT + HES].
odS
Outputs delay activation after power on: (0 to 255 min) this function is enabled after the
power-on of the instrument and inhibits any output activation for the period of time set in the
parameter.
power-on of the instrument and inhibits any output activation for the period of time set in the
parameter.
AC
Anti-short cycle delay: (0 to 50 min) minimum interval between a compressor stop and the
following restart.
following restart.
Rtr
P1-P2 percentage for regulation: 100=P1 only; 0=P2 only
CCt
Maximum duration for pull down: (0.0 to 23h50min, res. 10min) after elapsing this interval of
time the super cooling function is immediately stopped
time the super cooling function is immediately stopped
CCS
Differential for pull down: (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the
regulation SETPOINT is moved to SET+CCS (in normal mode) or to SET+HES+CCS (in
energy saving mode)
regulation SETPOINT is moved to SET+CCS (in normal mode) or to SET+HES+CCS (in
energy saving mode)
oHt
Overheating before activating the pull down function (when in normal mode): (1.0 to
12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function.
12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function.
oHE
Overheating before activating the pull down function (when in energy saving mode): (1.0
to 12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling
function.
to 12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling
function.
Con
Compressor ON time with faulty probe: (0 to 255 min) time during which the compressor is
active in case of faulty thermostat probe. With CY=0 compressor is always OFF.
active in case of faulty thermostat probe. With CY=0 compressor is always OFF.
CoF
Compressor OFF time with faulty probe: (0 to 255 min) time during which the compressor is
OFF in case of faulty thermostat probe. With Cn=0 compressor is always active.
OFF in case of faulty thermostat probe. With Cn=0 compressor is always active.
PROBE SETUP
ot
Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the first probe.
offset of the first probe.
P2P
Evaporator probe presence: n = not present; Y = the defrost stops by temperature.