8.1.5  Alarm relay 
With oAx=ALr the AUX relay operates as alarm relay. It is activated every time an alarm happens. Its 
status depends on the tbA parameter: if tbA=Y, the relay is silenced by pressing any key.  
If tbA=n, the alarm relay stay on until the alarm condition recovers. 
8.1.6  Activation during energy saving cycles 
With oAx=HES, the AUX relay is energised when the energy saving cycle is activated. 
FRONT PANEL COMMANDS 
 
 
 
Press to display target set point and the real set point. When in programming mode 
it selects a parameter or confirms an operation 
 
(ECO) To switch on and off the Energy Saving mode or the light output. Other 
functions related to par. LGC and LG2 
 
(UP) In programming mode it browses the parameter codes or increases the 
displayed value. Other functions related to par. UPC and UP2 
 
(DOWN) In programming mode it browses the parameter codes or decreases the 
displayed value. Other functions related to the par. dnC and dn2 
 
(ONOFF) Keep it pressed for 3 sec to switch on and off the device 
 
KEYS COMBINATION 
 
+
 
 
To lock or unlock the keyboard 
 
+
 
 
To enter in programming mode 
 
+
 
 
To return to room temperature display 
 
ICON 
MODE 
MEANING 
 
On 
Compressor enabled 
Flashing 
Anti-short cycle delay enabled (AC parameter) 
 
On 
Light output enabled 
 
On 
Ventilator output enabled 
Flashing 
Ventilator delay after defrost 
, 
 
On 
Measurement unit  
Flashing 
Programming mode 
 
On 
Energy saving mode active 
 
On 
An alarm condition is present 
Flashing 
Start-up operations are pending 
 
On 
Auxiliary output is activated 
 
NOTE: start-up operations lasts about 30 sec after powering on the device. At the end of this phase, 
the alarm icon will switch off if no alarm is active. 
9.1 
SET POINT MENU 
The SET key gives access to a quick menu where it is possible to see: 
the set point value 
the real set point value (rSE
Push and release the SET key five times or wait for 60 sec to return to normal visualisation. 
9.2 
CHANGE THE SETPOINT 
1. 
Push the SET key for more than 2 sec to change the Set point value; 
2. 
The value of the set point will be displayed and the “°C” LED starts blinking; 
3. 
To change the Set value push the UP or DOWN button. 
4. 
To memorise the new set point value push the SET key again or wait for 60 sec. 
9.3 
START A MANUAL DEFROST 
Push the DEFROST button for more than 2 sec to start a manual defrost. 
9.4 
CHANGE A PARAMETER VALUE 
To change the parameter values operate as follows:  
1.  Enter  the  Programming  mode  by  pressing  the  SET+DOWN  buttons  for  3  sec  (“°C  LED  starts 
blinking). 
2.  Select the required parameter. Press the SET button to display its value 
3.  Use UP or DOWN buttons to change its value. 
4.  Press SET to store the new value and move to the following parameter. 
 
To exit: Press SET+UP buttons or waits for 15 sec without pressing any key. 
 
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 
9.5 
ENTERING THE HIDDEN MENU 
The hidden menu includes all the parameters of the instrument. 
ENTER THE HIDDEN MENU 
1.  Enter the Programming mode by pressing SET+DOWN buttons for 3 sec (“°C or “°F” LED starts 
blinking). 
2.  Released the keys and then push again SET+DOWN buttons for more than 7 sec. The “L2”  label 
will be displayed immediately followed from the HY parameter.  
NOW YOU ARE IN THE HIDDEN MENU. 
3.  Select the required parameter. 
4.  Press the SET key to display its value 
5.  Use 
UP
 or DOWN to change its value. 
6.  Press SET to store the new value and move to the following parameter. 
 
To exit: Press SET+
UP
 or wait for 15 sec without pressing any key. 
 
NOTE1: if there are no parameters in L1, after 3 sec the “nP”  label will  be displayed. Keep the keys 
pushed till the “L2” message will be displayed. 
  
NOTE2: the previous set value will be stored even if the programming mode is exited by waiting for the 
time-out to expire. 
MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. 
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 
level) by pressing SET+DOWN. If a parameter is visible also in the First Level, in the HIDDEN MENU 
the decimal point will be lit. 
9.6 
LOCK THE KEYBOARD 
1. 
Keep both UP and DOWN buttons pressed for more than 3 sec. 
2. 
The “oFF” label will be displayed and the keyboard will be locked. If any button is pressed more 
than 3 sec, the “oFF” message will be displayed. 
9.7 
UNLOCK THE KEYBOARD 
Keep both UP and DOWN buttons pressed together for more than 3 sec till the “on” message will be 
displayed. 
9.8 
THE ON/OFF FUNCTION 
 
 
If onF = oFF, the instrument will be switched off by pushing the ON/OFF button. The 
OFF  message  will  appear  on  the  display.  In  this  configuration  the  regulation  is 
disabled. To switch the instrument on, push again the ON/OFF button. 
 
WARNING: any load connected to the normally closed contacts of the relays is always supplied 
from the main voltage, even if the instrument is in standby mode. 
10  PARAMETERS 
REGULATION 
Set 
Regulation Set Point: LS to US 
LS 
Minimum SET POINT: (-55.0°C to SET;  -67°F  to SET) sets the minimum value for the set 
point. 
US 
Maximum SET POINT: (SET to 150.0°C; SET to 302°F) set the maximum value for set point. 
HY 
Differential in normal mode (energy saving  mode not active):  (0.1 to  25.0°C; 1  to  45°F) 
differential for set point. Compressor Cut-IN is  
[SET-POINT + HY]. Compressor Cut-OUT is when the temperature reaches the set point. 
HYE 
Differential when energy saving mode is active: (0.1 to 25.0°C; 1 to 45°F) differential for set 
point. Compressor Cut-IN is [SET-POINT + HES +  HYE]. Compressor Cut-OUT is when the 
temperature reaches the [SET-POINT + HES]
odS 
Outputs  delay  activation  after  power  on: (0  to  255  min)  this  function  is  enabled  after  the 
power-on of the instrument and inhibits  any output  activation for the period of time set in the 
parameter. 
AC 
Anti-short cycle delay: (0 to  50 min) minimum interval  between a compressor stop and the 
following restart. 
Rtr 
P1-P2 percentage for regulation: 100=P1 only; 0=P2 only 
CCt 
Maximum duration for pull down: (0.0 to 23h50min, res. 10min) after elapsing this interval of 
time the super cooling function is immediately stopped 
CCS 
Differential for pull down: (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the 
regulation  SETPOINT  is  moved  to  SET+CCS  (in  normal  mode)  or  to  SET+HES+CCS  (in 
energy saving mode) 
oHt 
Overheating  before  activating  the  pull  down  function  (when  in  normal  mode):  (1.0  to 
12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function. 
oHE 
Overheating before activating the pull down function (when in energy saving mode): (1.0 
to  12.0°C;  1  to  21°F)  this  is  the  upper  threshold  limit  used  to  activate  the  super  cooling 
function. 
Con 
Compressor ON time with faulty probe: (0 to 255 min) time during which the compressor is 
active in case of faulty thermostat probe. With CY=0 compressor is always OFF. 
CoF 
Compressor OFF time with faulty probe: (0 to 255 min) time during which the compressor is 
OFF in case of faulty thermostat probe. With Cn=0 compressor is always active. 
PROBE SETUP 
ot 
Thermostat probe calibration:  (-12.0 to 12.0°C;  -21 to 21°F)  allows to  adjust any  possible 
offset of the first probe. 
P2P 
Evaporator probe presence: n = not present; Y = the defrost stops by temperature.