DIXELL S.r.l. 01XRCHC Manuale Utente

Pagina di 7
 
XRB60CHC EN r1.1 2018.11.01.docx 
                           XRB60CHC 
5/7 
 
d2d 
Digital inputs 2 alarm delay: (0 to 255) it is the delay between the detection of an  external 
event and the activation of the relative function. 
nPS 
Number  of  external  pressure  alarms  before  stopping  the  regulation:  (0  to  15)  after 
reaching nPS events in the digital input alarm delay (par. dxd) the regulation will be stopped 
and a manual restart (ON/OFF, power OFF and power ON) will be required 
odC 
Compressor and fan status after door opening: (no; FAn; CPr; F-C): no = normal;  
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF. 
rrd 
Regulation restart after door open alarm: (n; Y) n = no regulation if door is opened; Y = when 
did is elapsed, regulation restarts even if a door open alarm is present. 
LCi 
Light output controlled by digital input: (0 to 255) 
ENERGY SAVING  
ErA 
Energy  reduction  algorithm  used:  (nu;  bAS;  Aut)  nu=no  energy  saving  algorithm  used; 
bAS=basic energy saving algorithm; Aut=automatic energy saving algorithm. 
nbo 
Threshold for mode change (normal mode to energy saving mode): (0 to 10) 
HES 
Differential  for  energy  saving  mode:  (-30.0  to  30.0°C;  -54  to  54°F)  it  sets  the  increasing 
value of the set point during the Energy Saving cycle. 
LdE 
Energy saving mode controls the lights (lights off when energy saving goes active): (n; 
Y) the light status depends on the energy saving mode and is managed from ErA
Aid 
Period of analysis for ErA (valid if ErA=Aut): (1 to 20 days) set the interval of time for temperature 
variation analysis.
 
nCA 
Number  of  contiguous  cells  to  activate  Energy  Saving  (valid  if  ErA=Aut):  (1  to  20)  minimum 
pattern (1 cell = 30 min) without activity for energy saving activation 
nCC 
Number of contiguous cells with energy saving for Set-Point variation (valid if ErA=Aut): (1 to 
12) minimum interval of time for SET-POINT variation by steps (1°C or 1°F every 30 minutes) 
Pdt 
Automatic Pull Down after energy saving: (0 to nCC) energy saving mode is deactivated in advance 
(0=0min, 1=30 min) 
tun 
System tuning: L=low sensibility; H=high sensibility 
PPv 
Temperature probe used for temperature variation analysis: (P1, P2, P3, P4) which probe is used 
from Energy Reduction Algorithm 
FEn 
Force  status  change  from  energy  saving  mode  to  normal  mode  (valid  if  ErA=Aut):  number  of 
intervals with activity for mode changing 
FnE 
Force  status  change from normal  mode  to  energy saving  mode   (valid if ErA=Aut):  number  of 
intervals without activity for mode changing 
StE 
Period of time to switch from normal mode to energy saving mode (valid if ErA=bAS): 
(0.0 to 24h00min, res. 10 min) if door stay closed for StE time, the energy saving mode will be 
activated. NOTE: this will require a door switch to work. 
EtS 
Period of time to switch from energy saving mode to normal mode (valid if ErA=bAS): 
(0.0 to 24h00min, res. 10 min) maximum time for energy saving mode. NOTE: this will require a 
door switch to work. 
dS 
Door open time to switch from EtS to StE (valid if ErA=bAS): (0 to  999 sec) the energy 
saving mode will be immediately deactivated as soon as the door stay open more than the dS 
time. NOTE: this will require a door switch to work. 
TOTAL COUNTERS 
n1H 
Number of relay output 1 activations (thousands of) (read only) 
n1L 
Number of relay output 1 activations (hundreds of) (read only) 
n2H 
Number of relay output 2 activations (thousands of) (read only) 
n2L 
Number of relay output 2 activations (hundreds of) (read only) 
n3H 
Number of relay output 3 activations (hundreds of) (read only) 
n3L 
Number of relay output 3 activations (hundreds of) (read only) 
n4H 
Number of relay output 4 activations (thousands of) (read only) 
n4L 
Number of relay output 4 activations (hundreds of) (read only) 
n5H 
Number of digital input 1 activations (thousands of) (read only) 
n5L 
Number of digital input 1 activations (hundreds of) (read only) 
n6H 
Number of digital input 2 activations (thousands of) (read only) 
n6L 
Number of digital input 2 activations (hundreds of) (read only) 
n7H 
Number of digital input 3 activations (thousands of) (read only) 
n7L 
Number of digital input 3 activations (hundreds of) (read only) 
n8H 
Number of digital input 4 activations (thousands of) (read only) 
n8L 
Number of digital input 4 activations (hundreds of) (read only) 
F1H 
Number of working hours for relay output oA1 (thousands of) (read only) 
F1L 
Number of working hours for relay output oA1 (hundreads of) (read only) 
F2H 
Number of working hours for relay output oA2 (thousands of) (read only) 
F2L 
Number of working hours for relay output oA2 (hundreads of) (read only) 
F3H 
Number of working hours for relay output oA3 (thousands of) (read only) 
F3L 
Number of working hours for relay output oA3 (hundreads of) (read only) 
F4H 
Number of working hours for relay output oA4 (thousands of) (read only) 
F4L 
Number of working hours for relay output oA4 (hundreads of) (read only) 
BLUETOOTH 
rPS 
Reset owner password:  (n;Y) select and confirm YES for reset Owner Password and come 
back to default factory configuration. NOTE: remember to cancel the device also from the Cloud 
database  (click  on  “Delete”  link  present  on  the  right  of  the  appliance  card  present  on  the 
“Permissions” webpage. 
OTHER 
Adr 
Serial address for Modbus communication: 1 to 247 
bAU 
Baudrate: (9.6; 19.2; 38.4; 57.6) select the correct baudrate for serial communication (wired)  
LGC 
Light button configuration: nu=not used; ES=change working mode from normal to energy 
saving  mode  and  vice-versa;  LiG=light  output  control;  AUS=auxiliary  output  control; 
dEF=defrost control; Pb2=probe 2 value visualization  
LG2 
Light  button  configuration  (timed,  3  sec):  nu=not  used;  ES=change  working  mode  from 
normal to energy saving mode and vice-versa; LiG=light output control; AUS=auxiliary output 
control; dEF=defrost control; Pb2=probe 2 value visualization; ErA=reset of Energy Reduction 
Algorithm pattern 
dnC 
Down button configuration: nu=not used; ES=change working mode from normal to energy 
saving mode and vice-versa; oFF=device ON/OFF control; Cnt=counter menu 
dn2 
Down  button  configuration  (timed  3  sec):  nu=not  used;  ES=change  working  mode  from 
normal  to  energy  saving  mode  and  vice-versa;  oFF=device  ON/OFF  control;  Cnt=counter 
menù  
uPC 
UP  button  configuration:  nu=not  used;  AUS=auxiliary  output  control;  dEF=defrost  control; 
Cnt=counter menu  
uP2 
UP button configuration (timed 3 sec): nu=not used; ES=change working mode from normal 
to energy saving mode and vice-versa; CC=do not select it  
d1 
Probe P1 value visualization (read only) 
d2 
Probe P2 value visualization (read only) 
d3 
Probe P3 value visualization (read only) 
d4 
Probe P4 value visualization (read only) 
rSE 
Real Set point (SET + ES + oHx) 
FdY 
Firmware release: day (read only) 
FMt 
Firmware release: month (read only) 
FYr 
Firmware release: year (read only) 
rEL 
Firmware Release (read only) 
Ptb 
Parameter code table (read only) 
11  DIGITAL INPUT 
The free voltage digital input is programmable in different configurations by the i1F and i2F
DOOR SWITCH (ixF=dor) 
It signals the door status and the corresponding relay output status through the odC parameter:  
no = normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F-C = Compressor and fan OFF. 
Since the door is opened, after the delay time set through parameter  did, the door alarm is enabled, 
the display shows the message “dA” and the regulation restarts if rrd = Y. The alarm stops as soon 
as the external digital input is disabled again. With the door open, the high and low temperature alarms 
are disabled. 
START DEFROST (ixF=dEF) 
It starts a defrost if there are the right conditions. After finishing any defrost, the normal regulation will 
restart only if the digital input is disabled, otherwise the instrument will wait until the MdF safety time is 
expired. 
ENERGY SAVING (ixF=ES) 
The energy saving mode will be enabled / disabled with the digital input. 
MOTION SENSOR (ixF=MS) 
The external motion sensor activation is counted. 
AUXILIARY OUTPUT (ixF=AUS) 
The AUX output (if present and configured) will be enabled / disabled with the digital input. 
EXTERNAL WARNING ALARM (ixF=EAL) 
It is used to detect an external alarm. This signal does not lock the regulation. 
EXTERNAL LOCK ALARM (ixF=bAL) 
It is used to detect any critical external alarm. This signal locks immediately the regulation. 
EXTERNAL PRESSURE ALARM (ixF=PAL) 
It is used to detect any pressure external alarm. This signal  locks the regulation  after nPS events in 
dxd interval od time. 
REMOTE HOLYDAY MODE (ixF=HdF) 
It is used to force the holyday mode. 
REMOTE ONOFF (ixF=onF) 
It is used to switch ON and OFF the device remotely. 
12  INSTALLATION AND MOUNTING 
 
Instrument  XRB60CHC  shall  be  mounted  on  vertical  panel,  in  a 
29x71 mm hole, and fixed using the special bracket supplied. 
The  temperature  range  allowed  for  correct  operation  is  -20  to 
60°C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 
 
13  OPTIONAL FEATURES 
 
The MDP/CX rear cover can be used to increase the protection 
from water and dust. 
 
The HOT-KEY is used for a quick and easy upload (from device 
to  HOT-KEY)  or  download  (from  HOT-KEY  to  device)  of  the 
parameter map. 
 
The BLU serial interface converts the TTL output into an RS485 
signal that can be used to connect the unit to the controlling and 
supervising  system.  Please  note  that  standard  version  of  this 
converter does not work with XR-CHC devices. 
14  ELECTRICAL CONNECTIONS 
The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm
2
.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of  heavier 
loads use a suitable external relay. 
14.1 
PROBES 
The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the  evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination.