Honeywell International Inc. WFSADPT Manuale Utente
42
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013
Devices
Configuration and Programming
4. Place the faceplate over the module temporarily, and remove the faceplate again in less than 1
second. Do not attach the mounting screws for the faceplate during this step. The LED flashes
red light every half a second indicating that it is requesting a profile. The LEDs blink solid
green for ten seconds indicating that the profile is assigned.
Figure 3.2 Magnetic Sensor in a Module
3.6.2 Distributor Mode
Converting a Device into a Distributor
NOTE: Only a device with a profile can be made as a distributor.
To turn a device into a distributor, do the following:
1. Power up the device with one battery.
NOTE: Ensure that the device is in the profile modification mode. This is indicated by a single
yellow blink every 5 seconds. The profile modification mode times out if it has not received a
command in one minute.
yellow blink every 5 seconds. The profile modification mode times out if it has not received a
command in one minute.
2. Toggle the SLC code wheel address to pattern of 0-1-0-1. To toggle the SLC code wheel
address,
• Set the address to 0
• Change the address to 1
• Change the address back to 0
• Change the address back to 1.
• Change the address to 1
• Change the address back to 0
• Change the address back to 1.
NOTE: The LED flashes a single green every half a second when the device is functioning as a
distributor.
distributor.
Converting a Distributor Back into a Device
To turn a distributor device back to a network device, replace the battery and provide a proper code
wheel address. A normal device requires four batteries for trouble-free operation. It is recom-
mended to use fresh batteries after the distributor mode.