Honeywell International Inc. WFSADPT Manuale Utente

Pagina di 74
44
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0  10/10/2013
Devices
Device Operations
4. Click Extras and select Reset Devices. The Reset Devices screen appears, displaying the 
FWSG and other devices that have the profile assigned.
5. Click to select the required device and click Reset Device to remove the profile.
The profile is removed and the device is reset to factory default state.
3.7  Device Operations
3.7.1  Modes of Operation
Factory Default
In this mode, the devices are not associated with the FWSG. A profile must be assigned to associate 
the device with the FWSG. For further information on assigning a profile, refer to the topic, 
used for site survey.  Refer to Appendix A:, "Site Survey". 
The device cannot perform any fire protection in the factory default state. 
In this mode, the devices will be viewable in the communicator window of the PC tool with the 
state displayed as “Factory Default”.
Profile Assigned
In this mode, the devices are associated with the FWSG but are not an active participant in the 
mesh network. A device that is not in the tampered state can join the mesh network in formation or 
in the rescue mode. For further information on mesh formation, refer to the topic “Mesh Formation 
Mode” and for further information on rescue mode, refer to the topic “Rescue Mode”.  A device in 
the profile configured state can also be used to distribute profiles. For further information on dis-
tributing a profile, refer to  3.6.2 “Distributor Mode”.  To remove a profile from a device, refer to 
3.6.4 “Removing Profiles without PC-based Configuration Tool”.
A device cannot perform any fire protection until it becomes a part of the mesh network. The 
device will be an invalid reply or no answer at the FACP.
In this mode, the devices will be viewable in the communicator window of the PC tool and indi-
cates a status of “Profile assigned”.