Honeywell International Inc. WFSLCDUI Manuale Utente
46
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013
Wireless Display Driver (W-DIS-D)
W-DIS-D Operations
3.8 W-DIS-D Operations
Table 3.4 outlines the wireless related events and the location of display.
Table 3.4 Event Display Location Table
NOTE: One W-DIS-D is required for one W-GATE. Multiple W-GATE installations require a W-
DIS-D for each W-GATE.
DIS-D for each W-GATE.
3.8.1 W-DIS-D Operations
Modes of Operation Not in a Mesh Network
Bootloader
In this mode, the W-DIS-D cannot participate in a mesh and cannot provide fire protection. The W-
DIS-D will be available in the communicator window of the PC Tool with a status “Bootloader”.
To get a device out of bootloader, refer to the troubleshooting section.
DIS-D will be available in the communicator window of the PC Tool with a status “Bootloader”.
To get a device out of bootloader, refer to the troubleshooting section.
Factory Default
In this mode, the W-DIS-D is not associated with the W-GATE. For further information on assign-
ing a profile, refer to section 3.6.1. In this mode, the W-DIS-D will be viewable in the communica-
tor window of the PC tool with a state of “Factory Default”. The ANN-80 will display RF COMM
LOSS when the W-DIS-D is at Factory Default state.
ing a profile, refer to section 3.6.1. In this mode, the W-DIS-D will be viewable in the communica-
tor window of the PC tool with a state of “Factory Default”. The ANN-80 will display RF COMM
LOSS when the W-DIS-D is at Factory Default state.
Events
FACP
Annunciator
Alarm (Detector or Module
activations)
activations)
YES (Address specific to the
initiating device)
initiating device)
NO (No Display)
Tamper
YES (Generic Supervisory at GW
+1 address)
+1 address)
YES (Detailed display with SLC
address)
address)
RF related trouble conditions -
Jamming, Battery Low, Duplicate
address, Class-A missing second
link, Weak link low signal
strength.
Jamming, Battery Low, Duplicate
address, Class-A missing second
link, Weak link low signal
strength.
YES (Generic Trouble GW +2
address)
address)
YES (Detailed display with SLC
address)
address)
Wireless Device Missing from
network
network
YES (No Answer/Invalid response
for the specific SLC Address)
for the specific SLC Address)
NO
W-GATE initializing, wireless
mesh formation in progress.
mesh formation in progress.
YES (Generic Trouble GW +2
address)
address)
YES (no address specified)
Illegal address
YES (Generic Trouble GW +2
address)
address)
YES (address zero)
Mesh capacity exceeded
YES (Generic Trouble GW +2
address)
address)
YES (W-GATE base address)
RF comm loss
YES (No Answer/Invalid response
for the
for the
W-DIS-D
SLC Address)
YES
Normal
None
Mesh ID number