Pagina di 8
W8735ER WIRELESS OUTDOOR RESET MODULE
66-1202—01
2
WIRING
CAUTION
Do not mount the W8735ER on a metallic surface 
as this can interfere with reception.
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive 
loads such as motors, line starters, lighting ballasts 
and large power distribution panels.
Use shielded cable to reduce interference when 
rerouting is not possible.
1. Disconnect power.
2. Mount the Wireless Outdoor Temperature Control Mod-
ule with the supplied hardware.
3. Wire the 1, 2, and 3 terminals on the Outdoor Reset 
Module to the 1, 2, and 3 terminals on the EnviraCOM™ 
enabled thermostat (if available), Aquastat, Integrated 
Burner Control, SOLA, or anywhere on the bus where 
access to the EnviraCOM bus is available and conve-
nient. See Fig. 1.
4. Turn power on.
5. Bind the C7089R Wireless Outdoor Sensor to the Wire-
less Outdoor Reset Module. See “Sensor Binding” on 
Fig. 1. W8735ER Wireless Outdoor Reset Module wiring 
diagram.
C7089R INSTALLATION
Mount Outdoor Sensor
Before installing the C7089 sensor, make sure 2 AA (lithium 
preferred) batteries are inserted. See Fig. 2.
Fig. 2. Battery Installation
1. Mount the sensor bracket on a vertical wall. at least 6 
inches below any overhang. Choose a location pro-
tected from direct sunlight. See Fig. 3.
Fig. 3. Mounting the Sensor Bracket and Sensor
2. Mount the sensor bracket in the selected spot.
3. Once the sensor is bound to the W8735ER (see SEN-
SOR BINDING), place the sensor in the bracket, facing 
away from the wall.
M33912
5-9/16
(141)
5-1/32
(128)
1-1/4
(32)
4-9/16
(116)
4-13/32
(112)
X
3
2
1
W8735ER1000
Wireless
Outdoor Reset Module
POWER
WIRELESS SETUP
CONNECTED
CONNECT
FLASHING: CONNECTING TO REMOTE DEVICE(S)
GREEN: CONNECTED TO REMOTE DEVICES(S)
RED: REMOTE DEVICE(S) NOT COMMUNICATING
EnviraCOM
BUS
3
2
1
EnviraCOM
ENABLED
CONTROL
M32937
M28491
M28849A