Honeywell International Inc. AZWDGL Manuale Utente

Pagina di 30
Installatio
n
 and
 Ope
ratio
ns Guid
AZW-5
000
24
  
   
    
   
    
   
    
   
    
   
    
   
    
   
    
   
© Hon
e
y
w
el
l   
   
    
   
    
   
    
   
 LTB
T
-TM-A
Z
WIOG
Rev
. 0
0
0
1
B
E
T
A
Appendix A: AZW-5000 AVs and BVs
AZW-5000 points sorted by point number
Point
Function
Description
Default
Value
R/W
Comments
AV–0
through
AV-7
Commissioning ZigBee PAN ID
r/w
AV–8
through
AV-23
Commissioning ZigBee Security Key
r/w
AV–24
Commissioning ZigBee Group ID
r/w
AV–25
Commissioning WTS Set Point Adjustment Limit. 
r/w
Defines the relative set point range for WTS set point. Value X represents set 
point range of –X to +X). User can set it between 0 and 100.
AV–26
Commissioning ZigBee Device Type (0 
=coordinator, 1 = transceiver)
r/w
AV–27
Commissioning BACnet Device instance
r/w
AV–28
Commissioning BACnet MS/TP Network Number
r/w
AV–29
Commissioning BACnet ZigBee Network Number
r/w
AV–30
Commissioning MS/TP Baud Rate
r/w
Valid values are 0 (auto), 9600, 19200, 38400, 76800.
AV–31
Commissioning Internal Antenna Selection 
(0=vertical, 1=horizontal)
r/w
AV–32 AZW-5000 
diagnostics
ZigBee Channel Number
r
AV–33
through
AV-40
AZW-5000 
diagnostics
ZigBee Extended PAN ID (128 
bit) 
r
AV–41
through
AV-56
AZW-5000 
diagnostics
ZigBee Master Key
r