Honeywell International Inc. 8DL5821 Manuale Utente

Pagina di 4
K9947  7/04  Rev. A 
ALPHA 
 
ADEMCO 5821 
Temperature Sensor &  
Flood Detector 
INSTALLATION AND SETUP GUIDE 
GENERAL INFORMATION 
The ADEMCO 5821 Temperature Sensor & Flood Detector 
is a wireless transmitter used with ADEMCO alarms 
systems that support 5800 series devices.  The 5821 can be 
configured to operate as either a Temperature Sensor or 
Flood Detector.  The 5821 in combination with the 
ADEMCO T280R is ideal for monitoring refrigerators and 
freezers in restaurants, kitchens and warehouses where 
food storage is a concern.  The 5821 will send an alarm to 
the control when the set temperature limit is exceeded or 
when a flood is detected protecting equipment, property, 
and perishable items via it’s rf transmitter.   
Temperature Sensing is measured by an internal sensor, or 
externally using ADEMCO T280R probe, or both.  Flood 
detection is accomplished using external probe ADEMCO 
470PB with the supplied resistor.   
When the temperature either increases past the high 
threshold limit and delay (30 minute delay) or below the low 
temperature threshold limit and delay (30 minutes) an 
alarm is triggered.  This preset delay offers greater 
reliability against false alarms due to normal usage of 
refrigeration equipment.   
MODES OF OPERATION 
The refrigeration mode of the device can be used to monitor 
refrigerator or freezer equipment that keep perishables 
below a set temperature point. The warm temperature mode 
of the device is used to warn of a high temperature 
condition, protecting temperature sensitive equipment and 
operations. When the temperature rises to the set point 
temperature, an alarm is sent.   
Setting the temperature for Alarm.   
 
When the set temperature limit is exceeded, the appropriate 
predefined time-delay begins.  At the end of the delay, the 
alarm is sent.   
The 5821 can be used to operate in several modes as follows:   
•  Report room air temperature has fallen below 45°F.   
•  Report room air temperature has exceeded either 75°F 
or 95
°F as selected via the positioning of Dip Switch 1 
and 2.   
•  Monitor and report temperatures above 10°F or 42°F 
using ADEMCO External Sensor Probe T280R as 
selected via the positioning of DIP Switch 1 and 2.   
•  Monitor and report the presence of water using 
ADEMCO External Probe 470PB with supplied resistor 
as selected via the position of DIP Switch 2.   
The 5821 also feature a tamper switch, which causes a 
trouble signal to be sent to the control if the unit’s cover is 
removed from the base.   
The Tamper switch is also used when programming the 
unit’s serial number at the control.  
The 5821 is powered by a 3-volt lithium battery.  If the 
battery voltage gets too low, the 5821 sends a low battery 
signal to the control panel.   
Installing/Replacing  the Battery 
Important Notes:   
•  Use 3-volt lithium battery:   
Duracell DL 123A or  
Panasonic/Sanyo/Varta CR123A.   
•  Observe polarity.   
•  When replacing the battery, wait at least 30 seconds 
after removing the old battery, before installing the new 
one.   
1.  Remove the transmitter's top cover by inserting the flat 
blade of a small screwdriver into the pry-off slot at one 
end of the unit (see Fig. 1 for location), and slightly 
twisting the blade until the cover disengages.   
2.  Install a 3-volt lithium battery as shown in Figure 1.   
 
Operating 
Mode 
Cold Temp 
Mode 
<45
°F 
Warm Temp 
Mode 
>75
°F 
Hot 
Temp Mode 
>95
°F 
Refrig 
Mode  
>42
°F 
Freezer 
Mode >10
°F 
Flood 
Mode  
TAMPER  
Mode 
Loop Number 
Loop 1 
Loop 2 
Loop 2 
Loop 2 
Loop 2 
Loop 3 
Loop 4 
Sensor Device 
Internal 
Sensor 
Internal 
Sensor  
Internal 
Sensor  
External 
Probe 
T280R 
External 
Probe 
T280R 
External 
Probe 470PB 
with resistor 
PC Board 
Mounted 
Tamper 
Switch 
S1 
X  OFF 
OFF ON OFF  X 
Dip 
Switch 
Setting 
S2 X 
OFF 
ON 
ON 
On 
ON 
X = Switch position does not matter