5.5 Installation of sensors
For proper installation of the sensors on site, the operator must 
ensure that the following requirements are met:
l
ocation
 
of
 
installation
•  The sensors are secured to the machine with the supplied M8 
threaded bolt or with a suitable mounting adapter. 
•  Observe the rules for the choice of measurement locations for 
vibration measurements.
P
ermissible
 
ambient
 
conditions
Temperature: 
– 40 °C to +125 °C
Relative air humidity: 
max. 95 %, non-condensing
The sensors must not be installed in a location that is near a strong 
electromagnetic field (e.g. generator, high-voltage cable, electric 
drive unit, etc.).
t
ools
 
and
 
materials
•  Mounting adapter: Screw adapter (VIB 3.480*), adhesive adapter 
(VIB 3.418), magnetic adapter (VIB 3.423). For special tools and 
auxiliary materials required for the attachment of the various 
adapters, see chapter for adapter installation.
•  Standard tools for electrical installation (wire cutter, cable 
 stripper,  screwdriver).
•  Suitable strain relief devices for cables.
5.5.1 Choosing the measurement locations
When choosing a location of installation for a sensor observe the 
following rules to ensure optimum signal transmission:
•  Mount sensor in radial measuring direction (i.e. perpendicular to 
shaft, in vertical or horizontal position).
•  Axial measurement locations are recommended to monitor 
the  machine for the following defects or faults: Misalignment, 
 damaged geared wheels, loose fixtures, bent shafts, etc.
•  Machines mounted on rigid foundations show high horizontal 
vibration. Fixed anchoring suppresses vertical vibration.
•  Machines mounted on vibration-damped foundations show 
vibration that is equally strong in horizontal and vertical direc-
tion.
•  The frequency behavior and dynamic range of the sensor can 
be significantly influenced by the way the sensor is attached. 
Weak coupling to the measurement location results in attenu-
ated signals and limits the frequency range. The sensor must be 
secured to the measurement location in a rigid, friction-locked 
Installation and commissioning