Honeywell International Inc. WFSPS Manuale Utente
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
11
Specifications
FWSG FlashScan Wireless System Gateway
2.3 Specifications
Following are the specifications of the wireless gateway.
2.3.1 Environmental Specifications
2.4 Magnet Sensors
2.4.1 Profile Magnetic Sensor
The profile magnetic sensor (refer to Figure 2.2) is used to create a unique profile upon start-up. It can also be used to start profile distri-
bution for a gateway that contains a profile. The LED next to the profile magnet sensor turns on green for ½ a second when the sensor is
activated.
activated.
2.4.2 Mesh Formation Magnetic Sensor
The mesh formation magnetic sensor (refer to Figure 2.2) transitions the gateway in and out of mesh formation mode. The initial activa-
tion of the sensor puts the gateway in mesh formation mode (as long as it contains a profile). A subsequent activation of the magnetic
sensor transitions the gateway out of mesh formation and into the initial mesh restructuring and normal mode. The gateway can be
placed back into mesh formation mode by activating the magnet sensor once again. The LED next to the profile magnet sensor turns on
sensor transitions the gateway out of mesh formation and into the initial mesh restructuring and normal mode. The gateway can be
placed back into mesh formation mode by activating the magnet sensor once again. The LED next to the profile magnet sensor turns on
green for ½ a second when the sensor is activated.
The Mesh formation magnetic sensor can also be used to create a profile on start-up for a gateway that does not already contain a profile.
The Mesh formation magnetic sensor can also be used to create a profile on start-up for a gateway that does not already contain a profile.
Specifications
Data
External Supply Electrical Ratings
18V-30V
SLC Electrical Ratings
15V-30V
Maximum current when using the external supply
40mA
Maximum current when using the SLC power supply
24mA
Maximum SLC Resistance
50
Ω
Minimum signal strength level needed at the receiver for a primary path with weak
link trouble reporting enabled.
link trouble reporting enabled.
-55dBm
Minimum signal strength level needed at the receiver for a secondary path or
primary path with weak link trouble reporting disabled.
primary path with weak link trouble reporting disabled.
Must be 18 dBm higher than the noise
floor down to a minimum of -80dBm
floor down to a minimum of -80dBm
1
1
Ensure that the primary path signal strength level is within recommended guidelines to assure proper communication in the
mesh network.
Maximum ambient noise level
-85dBm
Maximum RF Power Output
+17dBm (Tx power level without antenna)
Radio Frequency
Lower ISM Band (902 - 928MHz).
System
Operating Temperature
StorageTemperature
Humidity
Gateway
0°C-49°C / 32°F-120°F
-10°C- 60°C / 14°F-140°F
10 to 93% RH, Non-condensing
Figure 2.2 LEDs and Magnetic Sensors on the FWSG