Honeywell International Inc. WFSPS Manuale Utente

Pagina di 64
34
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
Wireless Devices
Configuration and Programming
8.
Select the device from the Communicator panel. 
9.
Click Assign.
The device is now included in the list of devices with a profile assigned. When the profile is assigned, the green LEDs turn on steady for 
10 seconds.
3.5.2  Distributor Mode
Converting a Device into a Distributor
To turn a device into a distributor: 
1.
Power up the device with one battery installed. 
2.
Ensure that the device is in the profile modification mode. If the device is in profile modification mode, the yellow LED will blink 
once every 5 seconds. The profile modification mode times out if the device has not received a command in one minute.
3.
Alternate the SLC address wheel between 0-1-0-1. To turn the SLC address wheel, use a flathead screwdriver to adjust the rotary 
switches on the device to:
1.
Set the address to 0.
2.
Change the address to 1.
3.
Change the address back to 0.
4.
Change the address back to 1.
Converting a Distributor Back into a Device
To return a distributor device back to a network device, replace the batteries and provide a proper SLC address. A normal device requires 
four batteries for proper operation. It is recommended to use fresh batteries after the distributor mode. 
3.5.3  Mesh Formation
To add a device to a mesh, refer to the topic, "Create a Mesh Network". To form a mesh network, ensure that the gateway is powered on 
and contains a profile. Activate the mesh formation (refer to Figure 2.2) magnetic sensor on the gateway.
Repeater
The SWIFT Network does not require the use of a dedicated repeater as all wireless devices act as repeaters. When the repeater function 
is needed in a location where no specific fire function is required, a wireless monitor module or another device can be installed to act as 
a repeater.
3.5.4  Restoring a Device to Factory Default
Removing Profiles Without Using SWIFT Tools
A device can be restored to factory default state:
1.
Start with the device powered off. The process is performed during start-up.
2.
Power on the device by inserting a single battery into any slot in the device. The LEDs will blink yellow twice every five seconds 
for one minute after inserting the battery.
Figure 3.4  Selecting a Device
assi
gnp
ro
fil
e
.png
Figure 3.5  Assigning a Profile
assi
gnp
ro
fil
e
2.
pn
g
NOTE: Only a device with a profile can be used as a distributor.
NOTE: The green LED blinks every half second when the device is functioning as a distributor.